Linkage Grouping
Table 5-29 FusionModule800 linkage grouping
Linkage
Category
Default
Status
Function
Link
emergency
ventilation
with
Cabinet
Electronic
Clasp lock
open
off
When this linkage status is set to on:
● If the smart cooling product communicates
properly but does not provide the cooling function,
and the temperature in the cold aisle is greater
than or equal to the preset value (30°C by default),
the rear door of the IT cabinet automatically opens.
● If all smart cooling products fail to communicate,
and the temperature in the cold aisle is greater
than or equal to the preset value (30°C by default),
the rear door of the IT cabinet automatically opens.
● If the rear door of the IT cabinet is open and the
temperature in the cold aisle is higher than the
preset value (35°C by default), the front door of
the IT cabinet automatically opens.
● If at least one smart cooling product is in cooling
mode or the temperature in the cold aisle is lower
than the preset temperature (30°C by default)
minus 2°C, the ECC800-Pro reports a critical alarm
to remind the customer to close the door manually.
The alarm is cleared after the door is closed.
NOTE
● After the IT cabinet door automatically opens, a door
open alarm is displayed on the active alarms page of
the ECC800-Pro.
● In the Linkage Group area, click Link emergency
ventilation with cabinet electronic clasp lock open.
Click
to expand the Linkage Logic List. Click
in the Operation column to modify the temperature
setting.
Link smoke
alarm with
Cabinet
Electronic
Clasp lock
open
off
When this linkage status is set to on:
● If a smoke alarm is generated, the rear cabinet
door is opened.
● When the cabinet door is opened, the ECC800-Pro
generates a door open alarm. After the smoke
alarm is cleared, you need to manually close the
door. After the door is closed, the door open alarm
is cleared.
● If the emergency heat dissipation control logic
conflicts with the smoke alarm control logic, the
smoke alarm control logic takes precedence.
NOTE
If the fire extinguishing system is installed inside the
smart module, the linkage function is not enabled.
FusionModule800 Smart Small Data Center
User Manual
5 Power-On Commissioning
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
333