Maintenance Item
Operation
Expected Result
Troubleshooting
Operating
environment
● Ambient
temperature: –20°C
to +65°C
● Humidity: 0–95%
RH (non-
condensing)
If the humidity and
temperature are
abnormal, check the
smart cooling product
status.
Monitoring module
indicator
The module indicator
is steady green or
blinking green.
If the indicator is off
or any abnormal
condition occurs, see
to
rectify the fault.
Network interface
indicator
The green indicator is
steady on, and the
yellow indicator is
blinking.
If the indicator status
is abnormal, check the
network cable
connection.
Monitor interface
(network
management system
or WebUI)
Export smart cooling
product logs, alarms,
temperature, humidity,
as well as the
operating status and
time of the water
sensor, door status
sensor, temperature
sensor, and smoke
sensor from the
management system.
View the historical
alarms generated in
this month and select
the most common five
ones.
If an alarm is
generated, handle the
alarm by referring to
or
contacting Huawei
technical support.
Cable connection
The cable connections
are secure.
Secure loose cables.
-
Cables are not
damaged.
Replace the cables.
FusionModule800 Smart Small Data Center
User Manual
6 O&M