Component
Alarm Name
Alarm
Severit
y
Possible Cause
Measures
Teamwork
networking failed
Major
1. The DIP switch is set
incorrectly for
teamwork.
2. The teamwork
cables are loose or
damaged.
3. Any two smart
cooling product units
have the same
address.
4. No smart cooling
product unit is
configured as the
master unit.
5. The master unit is
powered off.
6. The ETH converter is
faulty.
7. The smart socket is
faulty.
8. The cables are faulty
between the smart
cooling product and
the smart socket or
monitoring host.
1. Set the DIP switch
correctly for
teamwork.
2. Check the teamwork
cables.
3. Change the
addresses of the
smart cooling
product units.
4. Configure one smart
cooling product unit
as the master unit.
5. Power on the master
unit, or configure
another unit as the
master unit.
6. Maintain or replace
the ETH converter.
7. Maintain or replace
the smart socket
8. Maintain or replace
the cables between
the smart cooling
product and the
smart socket or
monitoring host.
FusionModule800 Smart Small Data Center
User Manual
6 O&M