Component
Alarm Name
Alarm
Severit
y
Possible Cause
Measures
Group units
number not match
Major
1. Teamwork settings
are incorrect for
slave units.
2. The number of
smart cooling
product units is
incorrectly set in the
master unit.
3. A slave unit is power
off or offline.
4. The ETH converter is
faulty.
5. The smart socket is
faulty.
6. The cables are faulty
between the smart
cooling product and
the smart socket or
monitoring host.
1. Modify teamwork
settings for slave
units to enable slave
units to join the
teamwork group.
2. Set the total number
of units on the
master unit to the
actual number of
units.
3. Check the cable
connection and
running conditions of
the slave units.
4. Maintain or replace
the ETH converter.
5. Maintain or replace
the smart socket.
6. Maintain or replace
the cables between
the smart cooling
product and the
smart socket or
monitoring host.
Power overvolt
Major
1. The power supply
voltage is high.
2. The outdoor control
board is faulty.
1. Check the power
supply voltage.
2. Maintain or replace
the outdoor control
board.
Power undervolt
Major
1. The power supply
voltage is low.
2. The outdoor control
board is faulty.
1. Check the power
supply voltage.
2. Maintain or replace
the outdoor control
board.
Floor water
overflow
Critical
1. Water exists on the
floor.
2. The water sensor is
faulty.
1. Check and clear the
water.
2. Maintain or replace
the water sensor.
Power overfreq
Major
1. The power supply
frequency is too
high.
2. The SPD three-phase
test board is faulty.
1. Check the power
supply frequency.
2. Replace the SPD
three-phase test
board.
FusionModule800 Smart Small Data Center
User Manual
6 O&M
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
379