3.2.3.4.2 (Optional) Intelligent PDU2000
The intelligent PDU2000 accurately and effectively monitors the real-time status
changes of the current, voltage, power, and electric energy of electrical devices in
the data center.
The intelligent PDU2000 needs to support the following monitoring functions:
●
Detect and display the input current.
●
Detect and display the total input current.
●
Detect and display the input voltage; display the voltage and current
alternately.
●
Provide remote input management.
●
Remotely query the input voltage, total input current, input power, and input
energy through a serial port.
●
Remotely query the PDU status through a serial port. The status that can be
queried includes normal input power, overcurrent, overvoltage, and
undervoltage, as well as the communication status (normal or abnormal) of
the monitoring board.
●
Remotely set the input overcurrent warning threshold, overvoltage alarm
threshold, and undervoltage alarm threshold through a serial port, or locally
set these parameters.
●
Working status indicator: The PDU has a built-in input status indicator, which
indicates the working status of the PDU.
●
Input alarm: If any of input overcurrent, overvoltage, and undervoltage occur,
the working status indicator indicates the fault, and an alarm is reported over
the Modbus port.
Figure 3-14 Intelligent PDU2000
Table 3-7 Technical specifications of the intelligent PDU2000
Item
Specifications
Function
Supports single-phase AC 200–240 V
power supply, twenty 10 A outputs,
and four 16 A outputs.
Dimensions (H x W x D)
1732 mm x 50 mm x 45 mm
Output quantity and system
20 x C13 + 4 x C19
FusionModule800 Smart Small Data Center