c.
Tap the smart cooling product to be set in the cabinet layout diagram.
d. Choose Real-time Data > OFF.
●
Method 2: Log in to the ECC800-Pro WebUI as user admin. Choose
Monitoring > Cooling > NetCol5000-A1 > Controls > Control Information,
choose Startup/Shutdown control > OFF, and then click Submit.
NO TE
1 in NetCol5000-A1 is variable and subject to changes with the smart cooling product
connection sequence. The displayed value prevails.
Step 2 Disconnect the power supplies from the smart cooling product control unit and
the outdoor unit after the smart cooling product shuts down over the EMS.
Step 3 Reclaim all the refrigerant from the system using a refrigerant retrieval device to
ensure that there is no pressure inside the system.
NO TE
Discharge the refrigerant if the local laws and regulations allow.
Step 4 Remove the left front panel and right rear panel of the outdoor unit, and remove
the thermal insulation cover to expose the compressor completely.
Step 5 Remove the nut from the connection box on top of the compressor using an 8 mm
socket wrench, and disconnect the cable.
Step 6 Remove the inductor cable and oil heating belt from the compressor.
Step 7 Weld from the suction and discharge pipe welding points shown in
,
, or
. Remove the discharge pipe that connects the
compressor to the oil separator, and then remove the suction pipe.
NO TICE
To avoid burning the internal components, other pipes, thermal insulation foam,
power cables, and labels, take protective measures, such as spreading wet cloth,
around the welding position.
Step 8 Remove the three bolts from the compressor base using a 13 mm socket wrench,
and remove the compressor.