No.
Indicat
or
Name
Description
4
/
Route I switch
status
indicator
● Steady green: route I switched on
● Off: route I switched off
● Steady red: route I switched on
abnormally
5
/
Route II switch
status
indicator
● Steady green: route II switched on
● Off: route II switched off
● Steady red: route II switched on
abnormally
6
II
Route II power
status
indicator
● Steady green: normal
● Steady red: abnormal
3.3 Cooling System
3.3.1 Technical Specifications
All models (indoor and outdoor units) of this product meet the environmental
protection requirements. The environmental protection mark is as follows.
Figure 3-17 Environmental protection mark
Table 3-9 Indoor unit technical specifications
Item
NetCol5000-A013HX0E1 (Excluding Heater and
Humidifier)
Power system
208 V AC–240 V AC 50 Hz/60 Hz 1 Ph+N+PE/2 Ph+PE
Voltage tolerance
If upstream voltage fluctuation exceeds the rated
voltage±10%, you are advised to add a voltage
regulator. Otherwise, the smart cooling product may
generate alarms frequently and fail to work properly.
Frequency tolerance
±3Hz
FusionModule800 Smart Small Data Center
User Manual
3 System Architecture
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
35