Performance data statistics: You can view historical data of devices to help
analyze data or problems.
●
Operation log: You can view logs of key operations, such as user login,
parameter modification, data export, device upgrade, and access control
events.
●
Data export: You can export historical data of the ECC800-Pro and some
southbound devices.
3.4.2.5 Linkage Control
●
Supports the linkage logic of aisle smoke alarms or high temperature alarms.
By default, the IT cabinet doors are opened through linkage by default.
NO TE
The aisle smoke sensor alarm cannot trigger the customer's fire extinguishing system. Only
dry contact alarm signals are provided.
●
If the protected area of the fire extinguishing system is in the smart module,
when a smoke alarm is generated, the door of the linked cabinet is not
opened. If the door is opened, an alarm (door status alarm) is generated.
●
If the protected area of the fire extinguishing system is outside the smart
module, when a smoke alarm is generated, key hardware devices on the rear
door of the linked cabinet are opened.
3.4.3 Key Hardware Devices
3.4.3.1 ECC800-Pro
3.4.3.1.1 Product Configuration
The ECC800-Pro data center controller is used to monitor the devices and
environment in the smart module. It consists of the power module and main
control module. You can insert and remove the power module.
Figure 3-24 ECC800-Pro
(1) Power module
(2) Main control module
Table 3-15 ECC800-Pro environmental specifications
Item
Specifications
Operating
temperature
–20°C to +50°C
FusionModule800 Smart Small Data Center
User Manual
3 System Architecture
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
45