Figure 4-43 Space requirements for installing an air baffle
●
Installing an outdoor unit on a wall, as shown in
Figure 4-44 Requirements for installing an outdoor unit on a wall
NO TE
● The bearing capacity of the support platform is more than 320 kg.
● Reserve no less than 300 mm from the left or right side of the outdoor unit for
maintenance personnel to walk.
● Grid structure is recommended to avoid the air exhaust and intake of the smart
cooling product being affected by the guardrail structure.
● The picture is only for reference, adjust based on the on-site situation if necessary.
(Optional) Multiple Outdoor Units
When multiple outdoor units are to be installed, if they cannot be installed against
a wall or the local outdoor temperature may be below –10°C (NetCol500-A018) or
0°C (NetCol500-A020) or –10°C (NetCol500-A021), place an air baffle at the air
intake side of each outdoor unit.
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)