Figure 4-69 Bottom drainpipe routing
NO TICE
After routing water pipes, secure them to the pipe assembly using cable ties, and
seal the cable hole using firestop putty.
----End
4.2.6.7 Injecting Nitrogen to Preserve Pressure
Context
NO TICE
● The leakage test with nitrogen described in this section is dedicated for testing
the leaks of the indoor unit and the pipes connected to it.
● The measuring range of the pressure gauge must be greater than or equal to
4.0 MPa, and the tolerance range of the rubber hose must be greater than or
equal to 4.5 MPa.
● During the pressure preservation process, do not remove the rubber hose and
pressure gauge; otherwise, nitrogen may leak.
FusionModule800 Smart Small Data Center
User Manual
4 Installation Guide
Issue 01 (2021-02-05)