Table 4-12 Cable binding interval
Cable Diameter (mm)
Binding Interval (mm)
< 10
150
10–30
200
> 30
300
1. Bind cables with a moderate force and ensure that cables are not misshapen
to prevent compromising the signal quality.
2. After binding cables, cut off the excess parts of cable ties and trim away any
burrs, as shown in
Figure 4-183 Cutting off the excess part of a cable tie
3. Do not use cable ties at a place where the cables are bent. Otherwise, the
cable cores may break due to strong stress, as shown in
Figure 4-184 Binding cables in a bending area
4. Ensure that the cable ties are wrapped and secured in the same direction and
do not generate interference with subsequent operations, as shown in
.