Signal cables and power cables are routed in different cable troughs to
separate electrical cables from ELV cables.
●
Signal cables are installed on the top of the front door of the cabinet, and
power cables are installed on the top of the rear door of the cabinet.
●
Cable troughs are installed on the top of cabinets for routing cables.
Figure 3-9 Cable trough
3.2 Power Supply and Distribution System
●
The Converged Cabinet houses the UPS input and output, IT load, smart
cooling product power distribution, and management system power
distribution, and supports single and dual power inputs.
●
The power distribution module, which is rack-mounted, includes the surge
protective device (SPD), UPS input, output, and maintenance bypass as well
as the power supply to IT loads and smart cooling products.
●
The N architecture of the UPS system is supported. IT power distribution
supports a maximum of four cabinets.
●
The air cooled smart cooling product consists of the indoor unit and outdoor
unit and is supplied with mains power.
●
The management system consists of the ECC800-Pro, VCN/IVS1800 (optional),
camera (optional), cabinet electronic clasp lock, temperature sensor,
temperature and humidity sensor (T/H sensor), smoke detector, and water
sensor. They are powered by the power supply and distribution system.
●
The 48 V lithium iron phosphate batteries are configured.
3.2.1 Technical Specifications
Table 3-3 Technical specifications
Category
Item
Specifications
Power supply
Input voltage range
342–456 V
Input frequency
50/60 Hz (±3 Hz)
Power
IT load power
consumption
● Normal temperature and low
temperature: 8.5 kW
● High temperature: 7 kW
FusionModule800 Smart Small Data Center
User Manual
3 System Architecture
Issue 01 (2021-02-05)