Figure 6-15 Removing the fan
Step 8 Install a new fan in the original position by performing the preceding steps in
reverse order, and install the air director and fan baffle plate (if any).
Step 9 After powering on the smart cooling product, log in to the ECC800-Pro WebUI as
user admin, choose Monitoring > Cooling > NetCol5000-A1 > Controls >
Control Information, set Startup/Shutdown control to ON, and click Submit.
Step 10 Choose Controls > Control Information, set Diagnostic mode to Enter, and click
Submit.
Step 11 Choose Running Parameters > Diagnostic Mode Parameters, set Indoor fan
manual control to 50%, and click Submit. If the indoor fan works properly and
there is no alarm, the indoor fan is functional. Set Indoor fan manual control to
0% and click Submit.
Step 12 Choose Controls > Control Information, set Diagnostic mode to Exit, and click
Submit.
Step 13 Clear up the indoor fan total runtime.
●
Method 1: Log in to the ECC800-Pro mobile phone or pad app as user admin.
a. Choose Home.
b. Tap the cabinet that houses the smart cooling product in the micro-
module view.
c.
Tap the smart cooling product to be set in the cabinet layout diagram.
d. Choose Real-time Data > Perf Maint, and clear up the indoor fan total
runtime.
●
Method 2: Log in to the ECC800-Pro WebUI as user admin. Choose
Monitoring > Cooling > NetCol5000-A1 > Controls > Performance
Maintenance Control, and clear up the indoor fan total runtime.
----End