Method 2: Log in to the ECC800-Pro WebUI as user admin. Choose
Monitoring > Cooling > NetCol5000-A1 > Controls > Performance
Maintenance Control, and clear up the condensate pump total runtime.
----End
6.4.3.1.3 Replacing a PSU, Rectifier, or Main Control Module
Prerequisites
●
A PSU, rectifier, or main control module needs to be replaced.
●
A spare PSU, rectifier, or main control module of the same model is available
and functional.
Context
●
The PSU, rectifier, and main control module can be replaced in the same way.
This section describes how to replace a PSU.
●
To replace the main control module, download the software and
ACC
Software Upgrade Guide
from Huawei websites, and upgrade it on the PAD or
ECC.
●
shows the front panel of a smart cooling product control unit.
Figure 6-17 Front panel of the smart cooling product control unit
(1) Ground point
(2) Rectifier
(3) PSU
(4) FE_2 port for connecting a
smart ETH gateway PoE or
LAN ports on the ECC
(5) FE_1 port for connecting a
smart ETH gateway PoE or
LAN ports on the ECC
(6) CAN_IN (input port of the
teamwork CAN and
northbound RS485 port)
(7) RS485/12 V port for
connecting the T/H sensor
(8) USB port
(9) DP (display port)
(10) COM/FE (northbound
RS485 port and FE port)
(11) CAN_OUT (output port of
the teamwork CAN and
northbound RS485 port)
(12) Main control module
Procedure
Step 1 Shut down the smart cooling product over the EMS.
●
Method 1: Log in to the ECC800-Pro mobile phone or pad app as user admin.
a. Choose Home.
b. Tap the cabinet that houses the smart cooling product in the micro-
module view.