a. Choose Home.
b. Tap the cabinet that houses the smart cooling product in the micro-
module view.
c.
Tap the smart cooling product to be set in the cabinet layout diagram.
d. Choose Real-time Data > OFF.
●
Method 2: Log in to the ECC800-Pro WebUI as user admin. Choose
Monitoring > Cooling > NetCol5000-A1 > Controls > Control Information,
choose Startup/Shutdown control > OFF, and then click Submit.
NO TE
1 in NetCol5000-A1 is variable and subject to changes with the smart cooling product
connection sequence. The displayed value prevails.
Step 2 Disconnect the power supply from the smart cooling product control unit after the
smart cooling product shuts down over the EMS.
Step 3 Remove the cover from the electric control box using a Phillips screwdriver, open
the compartment that houses the fuse, as shown in
, and remove the
fuse.
Figure 6-19 Removing a fuse
Step 4 Install a new fuse in the original position by performing the preceding steps in
reverse order.
Step 5 After powering on the smart cooling product, log in to the ECC800-Pro WebUI as
user admin, choose Monitoring > Cooling > NetCol5000-A1 > Controls >
Control Information, set Startup/Shutdown control to ON, and click Submit.
Step 6 Choose Controls > Control Information, set Diagnostic mode to Enter, and click
Submit.