Step 7 Choose Monitoring > Aisle > T/H Sensor Group and check whether the T/H
sensor works properly. If yes, the T/H sensor is functional.
Step 8 Choose Home > Plan View and add a new T/H sensor in the appropriate position.
----End
6.4.4.11 Replacing a Remote T/H Sensor (33010516)
Prerequisites
●
A T/H sensor needs to be replaced.
●
A spare T/H sensor of the same model is available and functional.
Context
A T/H sensor can be maintained only from the rear door.
Procedure
Step 1 Tap Shutdown on the controller home screen.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
controller home screen.
Step 2 Remove the cables from the T/H sensor.
NO TICE
After removing cables, wrap exposed terminals with insulation tape and do not
block cable labels. If cable labels are blocked, cables may be connected incorrectly
later.
Step 3 Remove the faulty T/H sensor.
Step 4 Attach the new T/H sensor to an appropriate position on the IT cabinet door
frame based on site requirements.
Step 5 Reinstall the cable removed from the T/H sensor.
NO TE
Before removing a T/H sensor, remember the DIP switch setting on it. When you install a
new T/H sensor, you need to set the same DIP switch setting for the new one.
----End
FusionModule800 Smart Small Data Center
User Manual
6 O&M
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
471