Figure 6-70 Connecting a new water detection cable
(1) Conversion cable end B, connected to the
water detection cable
(2) Water detection cable end A, connected to
the conversion cable
NO TE
The water detection cable and conversion cable are interconnected through the male and
female connectors.
Step 3 Connect the network cable between the water detector and ECC800-Pro, immerse
the water detection rope in water, and check whether an alarm is generated. If an
alarm is generated, the component is functional.
----End
6.4.4.15 Replacing an Electrode Water Sensor
Prerequisites
●
Recommended tools and materials: Phillips screwdriver, crimping tool
●
A water sensor needs to be replaced.
●
A spare water sensor is available.
Procedure
Step 1 Disconnect the cable between the water sensor and the ECC800-Pro.
Step 2 Remove the faulty water sensor.
Step 3 Place the new water sensor in the correct position.
Step 4 Connect the water sensor cable connected to the ECC800-Pro to the new water
sensor.
----End
6.4.4.16 Replacing an eLight Strip Light
Impact on the System
The eLight strip light is off during replacement.
FusionModule800 Smart Small Data Center
User Manual
6 O&M
Issue 01 (2021-02-05)
Copyright © Huawei Technologies Co., Ltd.
478