FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
7 System Commissioning
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
43
Figure 7-10
Removing the detector
4.
Verify that the fire alarm control panel has reported a zone fault, as shown in
Zone 1 and 2 respectively indicate fault alarms for the smoke and heat detectors.
Figure 7-11
Fault alarms on the fire alarm control panel
5.
Hold the smoke detector body, align the smoke detector indicator with the position
shown by (1) in
, and turn the detector body clockwise to the position shown
by (2) in
to install the smoke detector.
Reinstall the heat detector in a similar way as reinstalling the smoke detector, as shown in
After the smoke detector or heat detector is reinstalled, the corresponding fault indicator turns off in
about 3s.