FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
7 System Commissioning
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
44
Figure 7-12
Smoke detector installation reference line
Figure 7-13
Heat detector installation reference line
Step 11
Press
RESET
to reset the fire alarm control panel.
Step 12
(Optional) Check whether the fire alarm signals are reported to the management system.
Step 13
Reconnect cables to the electromagnetic valve.