FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
65
Remote T/H sensors are configured before delivery. You just need to verify the settings against the
cooling device initial configuration table.
Procedure
Step 1
Verify the DIP switch settings for the remote T/H sensors of each air-cooled precision smart
cooling product by referring to the cooling device initial configuration table.
Step 2
If any setting is inconsistent with the initial setting, change it to the initial setting.
----End
8.2.2 Teamwork Initial Configuration
Prerequisites
You have powered on the air-cooled precision smart cooling products.
Preparations
Tools: none
Documents: cooling device initial configuration table, smart cooling product teamwork
relationship diagram, management system initial configuration table
Skill requirement: cooling engineer
For the diagrams and tables, see the initial configuration parameter manual for the solution in
use.
Context
Teamwork is a solution for allocating the overall temperature and humidity of the
FusionModule1000. It is used to improve the operating efficiency of precision smart cooling
products by preventing competitive operations.
Multiple precision smart cooling products are interconnected and centrally controlled to
support the rotation of active and standby precision smart cooling products. A maximum of 32
precision smart cooling products can be interconnected using the CAN bus. The precision
smart cooling product whose address is displayed as 1 on the LCD is the master, which
collects, processes, and delivers data.
shows the teamwork topology for air-cooled precision smart cooling products.