FusionModule1000A40 Prefabricated All-in-One Data
Center
Commissioning Guide
8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
72
8.2.3 Initial Configuration of Temperature and Humidity
Prerequisites
You have powered on the air-cooled precision smart cooling products.
Preparations
Tools: none
Documents: management system initial configuration table, cooling device layout diagram,
cooling device initial configuration table
Skill requirement: cooling engineer
For the diagrams and tables, see the initial configuration parameter manual for the solution in
use.
Context
Smart cooling products in one module constitute a group. You need to set the temperature and
humidity of the smart cooling product system on the master unit in each group before smart
cooling products in the group are used.
Procedure
Step 1
On the home screen, choose
Settings
>
System Settings
>
T/H Sensor.
To change the settings, you need to log in as the
Admin
user. For the password, see the management
system initial configuration table.
You need to obtain permission before changing system settings. Only trained and qualified personnel
can change settings excluding the control type and set point of the T/H sensor.
Figure 8-8
Setting temperature and humidity values