8 Commissioning Core Components
Issue 02 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
58
Figure 8-1
Login screen
The user name is admin, and the password is 000001.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
3.
In the displayed dialog box, tap
Yes
to start the inverter, as shown in
Figure 8-2
Starting the inverter
You can also choose
System Info
>
Maintenance
. In the
Maintenance
screen, start the inverter.
Step 5
After the inverter starts, the UPS works in normal mode. The Bypass mode alarm disappears
from the MDU. Check that the UPS has transferred to normal mode by viewing the system
running diagram.
Step 6
Set battery parameters.
On the UPS main monitoring screen, tap
System Info
>
Settings
>
Basic Param.
and set the
battery capacity and number of cells based on the actual configurations. A 2 V battery is a cell.
If a battery is 12 V, the number of cells is equal to the number of batteries multiplied by 6. If a
battery is 2 V, the number of cells is equal to the number of batteries.