Figure 5-95
Closing the panel
Step 9
Confirm the replacement.
1.
Perform a post-replacement inspection.
After the parts replacement, return to the SmartKit page and click
Replaced
. Then
complete the check after the replacement as prompted.
2.
Check system status.
On the
Parts Replacement
page, click
Inspection
to check the system status again. If
any inspection item fails, rectify the fault based on the suggestions in the inspection
report.
3.
After the preceding procedure is complete, check services on the host for any storage-
related error.
----End
Follow-up Procedure
After the fan module is replaced, label it to facilitate subsequent operations.
5.10.2 Replacing a Fan Module (for Dorado18000 V3)
This section describes how to replace a fan module.
Impact on the System
During the replacement of a fan module, the system's heat dissipation is affected and the
system temperature increases. If the controller reaches the self-protection threshold (for
OceanStor Dorado V3 Series
Parts Replacement
5 Replacing FRUs
Issue 05 (2019-01-30)