l
If the indicator is steady green, the fan module is successfully installed.
l
If the indicator is steady red or off, the newly installed fan module is faulty, the fan
module slot is faulty, or the fan module is incorrectly installed.
Figure 5-110
Running/Alarm indicator on a fan module
Step 8
Confirm the replacement.
1.
Perform a post-replacement inspection.
After the parts replacement, return to the SmartKit page and click
Replaced
. Then
complete the check after the replacement as prompted.
2.
Check system status.
On the
Parts Replacement
page, click
Inspection
to check the system status again. If
any inspection item fails, rectify the fault based on the suggestions in the inspection
report.
3.
After the preceding procedure is complete, check services on the host for any storage-
related error.
----End
Follow-up Procedure
Label the replaced fan module to facilitate subsequent operations.
5.13.3 Replacing a Data Switch
This section describes how to replace a data switch.
Impact on the System
During the replacement of a data switch, the data switch is powered off. This causes all I/O
forwarding workload to transfer to another data switch, degrading the system reliability.
Prerequisites
l
The spare part is ready.
l
The data switch to be replaced has been located.
l
Before the replacement, restore the password of account
ibc_os_hs
for each management
module, and data switch to the default one.
NOTE
For details about how to change the password of account
ibc_os_hs
, see the
Installation Guide
specific
to your product.
l
The cable connection position on the data switch to be replaced has been clearly marked.
OceanStor Dorado V3 Series
Parts Replacement
5 Replacing FRUs
Issue 05 (2019-01-30)
Copyright © Huawei Technologies Co., Ltd.