Figure 4-55
Closing the panel
Step 9
Confirm the replacement.
After the preceding procedure is complete, check services on the host for any storage-related
error. If any storage-related error is reported, contact Huawei technical support.
----End
Follow-up Procedure
After the fan module is replaced, label it to facilitate subsequent operations.
4.3.2 Replacing a Fan Module (for Dorado18000 V3)
This section describes how to replace a fan module.
Impact on the System
During the replacement of a fan module, the system's heat dissipation is affected and the
system temperature increases. If the controller reaches the self-protection threshold (for
example, the CPU temperature reaches 97°C), the controller is automatically powered off,
degrading the system reliability.
Prerequisites
l
The spare part is ready.
OceanStor Dorado V3 Series
Parts Replacement
4 Replacing CRUs
Issue 05 (2019-01-30)