Figure 5-52
Power indicator on an interface module
Step 11
Confirm the replacement.
1.
Perform a post-replacement inspection.
After the parts replacement, return to the SmartKit page and click
Replaced
. Then
complete the check after the replacement as prompted.
2.
Check system status.
On the
Parts Replacement
page, click
Inspection
to check the system status again. If
any inspection item fails, rectify the fault based on the suggestions in the inspection
report.
3.
After the preceding procedure is complete, check services on the host for any storage-
related error.
----End
Follow-up Procedure
After the interface module is replaced, label it to facilitate subsequent operations.
5.8 Replacing a Power Module
This section describes how to replace a power module.
5.8.1 Replacing a Power Module (for Dorado5000 V3)
This section describes how to replace a power module. Except that there is a slight difference
on removing and inserting power cables between AC and DC power modules, other
operations performed for them are the same. This section uses AC power modules as an
example.
Impact on the System
During the replacement of a power module, if the redundant power module fails, the system
services will be interrupted.
OceanStor Dorado V3 Series
Parts Replacement
5 Replacing FRUs
Issue 05 (2019-01-30)