High Voltage SF6 AC Circuit Breaker
30/30
Test before working
Technical
request
Test
result
Remark
Measuring spring store
energy time
≤
15s
Switch on time
75±8ms
Switch off time
30±3ms
Check the manual
operation device
Measuring
mechanical
characteristic
Check the trip prevent
device
Measuring the resistance of main loop
≤
40µ
Ω
Measuring insulation resistance
∝
Power frequency voltage withstand test
230kV
Alarm pressure
0.55MPa
Pressure test
Closedown pressure
0.50MPa
Circuit breaker leak check
≤
0.5%
9
Measuring moisture
≤
150ppm
10
Register the circuit breaker’s operating
times
11
Clear the locale, cover the cover board
12
Connect the primary busbar, ready to work
The user’s checker:
director
:
date
:
The manufacturer’s checker
:
director
:
date
:
The added test items of user required: