12
7. Adjustment Parameters
Parameter Item
Initial
Value
Function
Air End
2-A
Standard
Current
0000
Used to calibrate Air End 2;
For phase A current, enter the standard current value. The
controller will calculate the current coefficient based on
the division of user input value by current value currently
detected and save it. The standard current value is not
saved and only used to calculate the coefficient.
Coefficient
1.000
When calibrating the current, enter the coefficient.
Current value displayed on the controller = sampling
value × coefficient
Present
Current
***.*A
Display the value of current which is sampled and
calibrated by the controller. This value is a real-time
value and cannot be set.
Air End
2-B
Standard
Current
0000
Used to calibrate Air End 2;
For phase B current, enter the standard current value. The
controller will calculate the current coefficient based on
the division of user input value by current value currently
detected and save it. The standard current value is not
saved and only used to calculate the coefficient.
Coefficient
1.000
When calibrating the current, enter the coefficient.
Current value displayed on the controller = sampling
value × coefficient
Present
Current
***.*A
Display the value of current which is sampled and
calibrated by the controller. This value is a real-time
value and cannot be set.
Air End
2-C
Standard
Current
0000
Used to calibrate Air End 2;
For phase C current, enter the standard current value. The
controller will calculate the current coefficient based on
the division of user input value by current value currently
detected and save it. The standard current value is not
saved and only used to calculate the coefficient.
Coefficient
1.000
When calibrating the current, enter the coefficient.
Current value displayed on the controller = sampling
value × coefficient
Present
Current
***.*A
Display the value of current which is sampled and
calibrated by the controller. This value is a real-time
value and cannot be set.
Standard Temperature
0000
℃
When calibrating the exhaust temperature, enter the
standard temperature value. The controller will calculate
the temperature coefficient based on the division of user
input value by exhaust temperature currently detected and
save it. The standard temperature value is not saved and
only used to calculate the coefficient.