13
7. Adjustment Parameters
Parameter
Item
Initial Value
Function
Coefficient
1.000
When calibrating the temperature, enter the coefficient.
Temperature value displayed on the controller = (sampled
temperature value - zero) × coefficient
Zero
0000
℃
Compensate for the zero deviation of hardware.
Present
Temperature 2
0000
℃
Display the value of temperature which is sampled and
calibrated by the controller. This value is a real-time
value and cannot be set.
Standard
pressure
00.00MPa
When calibrating the exhaust pressure, enter the standard
pressure value. The controller will calculate the pressure
coefficient based on the division of user input value by air
supply pressure currently detected and save it. The
standard pressure value is not saved and only used to
calculate the coefficient.
Coefficient
1.000
When calibrating the pressure, enter the coefficient.
Pressure value displayed on the controller = sampled
pressure value × coefficient
Zero
00.00MPa
When the air supply pressure is less than the set value, it
will be displayed as 0.00MPa.
Present Pressure
00.00MPa
Display the value of pressure which is sampled and
calibrated by the controller. This value is a real-time
value and cannot be set.
Standard voltage
0000V
When calibrating the voltage, enter the standard voltage
value. The controller will calculate the voltage coefficient
based on the division of user input value by voltage value
currently detected and save it. The standard voltage value
is not saved and only used to calculate the coefficient.
Coefficient
1.000
When calibrating the voltage, enter the coefficient.
Voltage value displayed on the controller = (sampled
voltage value - zero) × coefficient
Present Voltage
0000V
Display the value of voltage which is sampled and
calibrated by the controller. This value is a real-time
value and cannot be set.
CURR MODE
DEBUG/ WORK
Set the update rate of current display; data is updated fast
in DEBUG mode; data is updated slowly in WORK
mode.
LED NUM
3LED
It is set to 3LED.