DIP-Switch
Use DIP-Switch for adjustment of Modbus®-address and termination. The DIP-switches have priority followed by the
parameters in the registers. As soon as the DIP-switch is on ‘0’ the address acc. Register 4x0764 (Modbus Baseaddress,
Default = 40) are valid. Changes of the DIP-switch are active after 5 seconds.
Modbus®-addressing
Modbus®-termination
1 = On
120
Ω
+ 1nF
0 = Off
Push-Button
Duration of operation
Function
5 ... 10 s
Zero point reset
10 ... 20 s
Reset to factory setting
Zero point reset
Reset pressure variations with the zero point reset.
Please remove pressure hoses before zero point reset.
During initial operation a zero-point reset is not necessary.
Reset to factory setting
Sensor is reset to delivered setting. Factory settings are listed in the register list – default values.
9
1
0
1
0
1 2 3 4 5 6 7 8
1
0
1
0
Address
0000 Baseaddress
0001 Basea 1
0010 Basea 2
1101 Basea 13
1110 Basea 14
1111 Basea 15
Format
00 = 1-8-E-1
01 = 1-8-O-1
10 = 1-8-N-1
11 = 1-8-N-2
Baud rate
00 = 9600
01 = 19200
10 = 38400
11 = 57600