©2017 Hubbell Incorporated | Chance

®

 Full Range ARVI Operating Instructions

Function and Design Overview

The CHANCE® Full-Range Auto-Ranging Voltage Indicator (ARVI), model number PSC4032915, is a 
portable tool to confirm that an AC (Alternating Current) high voltage circuit is energized or
de-energized prior to performing maintenance. It provides field practicality over the two points of 
contact measurement method. Readings from the Full-Range ARVI represent the class of voltage that 
is present on the line.

The Full-Range ARVI is used as a secondary means to confirm the condition of a circuit after 
principal work procedures such as visible open gaps, dispatcher hold orders, and apparatus tag-outs 
have rendered the circuit de-energized. The unit utilizes a single point of contact to the conductor, 
therefore it is not a voltmeter. It is designed to determine approximate Phase-to-Phase nominal 
voltage up to 765 kV AC 50/60 Hz.

The Full-Range ARVI is an electric field intensity indicator, which is calibrated to illuminate an LED 
(light-emitting diode) representing the class of voltage that is present on the conductor. It responds 
to the magnitude of the field gradient between its end probe and a floating electrode. The device 
may also indicate the combined field intensity from nearby conductors, including ground wires and 
grounded equipment. If the universal coupling is too close to a ground, another phase, or another 
voltage source, the voltage indication will tend to be high. If the universal coupling is too close to a 
jumper or equipment of the same phase, the indication will tend to be low. 

The tool must always be 

used with an appropriate length Hot Stick for safety and to maintain its calibration.

This device is an AC (alternating current/alternating voltage) only indicator; do not use it to detect 

DC (direct current/non-alternating voltage).

 NOTICE

Before and after each use, always test the unit on a known energized voltage source or with the 

Voltage Indicator Tester to verify proper operation.

!

 WARNING

Features

•  Meets intent of OSHA 1910.269 to test for absence of nominal voltage
•  Used to determine if power lines are at rated voltage, have induced voltage, or are de-energized
•  Capacitive Test Point through 765 kV AC for overhead and underground systems
•  Adjustable audible alarm
•  Power-saving sleep mode (auto-off)
•  Approximate Phase-to-Phase voltage ranges are indicated by LED lights
•  Automatic Hold Mode
•  Battery drawer for simple battery replacement
•  QR code located in the instructions and on the unit itself

This instrument is not a voltmeter; hence, the manufacturer claims no specific accuracy, and therefore, 
no specific accuracy is to be assumed by the user. Readings will vary with the field intensity, 
determined by a great variety of field conditions including proximity, size, and orientation of all system 
components in the vicinity, both energized and grounded. Erroneous readings may result from being 
too near other energized conductors or being too near another phase or ground. To avoid such field 
distortions, keep the unit as far away as practical from all system components other than the specific 
conductor being tested.

Accuracy

Summary of Contents for CHANCE PSC4032915

Page 1: ...evision A 02 17 Operating Instructions Model No PSC4032915 2017 Hubbell Incorporated hpsliterature hubbell com hubbellpowersystems com For use with Capacitive Test Point through 765 kV AC NOTICE Befor...

Page 2: ...dures techniques etc that if not followed carefully could RESULT IN DEATH A WARNING refers to operating procedures techniques etc that if not followed carefully could RESULT IN INJURIES OR DEATH A CAU...

Page 3: ...ered in relation to installation operation or maintenance Should additional information and details be desired or if situations arise which are not covered adequately for the user s purpose the specif...

Page 4: ...high If the universal coupling is too close to a jumper or equipment of the same phase the indication will tend to be low The tool must always be used with an appropriate length Hot Stick for safety...

Page 5: ...quivalent voltage ranges to provide indication of each of the Voltage Classes are as follows Voltage Class Voltage Range 600 V 480 V to 900 V 4 kV 1 kV to 6 5 kV 15 kV 6 6 kV to 17 kV 25 kV 18 kV to 2...

Page 6: ...sulators ground wires and any system components that may cause reading errors c The audible alarm will begin to beep as the unit senses the electric field The Range LED that corresponds with the syste...

Page 7: ...the electromagnetic action of current and electrostatic action of voltage can induce a high static condition on the de energized circuit Activity effects can exist between all conductor pairs The Ful...

Page 8: ...round equipment 1 When testing dead front URD equipment use an appropriate Bushing Adapter on the Bushing Well On Capacitive Test Points use the Straight Probe Never use the Shepherd Hook on URD equip...

Page 9: ...For live front install the small hex head machine screw 1 4 20 X 3 8 long Minimum Approach Distances MAD should be adhered to at all times a Ensure that the green PWR LED is flashing before during an...

Page 10: ...tive Test Points must be free of corrosion and contamination for valid testing 2 While observing all required safe work practices and with an appropriate length insulated Hot Stick attached to the Ful...

Page 11: ...ll the elbow with elbow puller tool then orient the elbow so it is safely accessible for testing 2 Utilizing all safe practices and procedures Operator 2 with the installed elbow adapter on the Full R...

Page 12: ...unit then will return to the normal audible mode but one LED will remain solid until reset To reset the unit after a held reading is displayed Remove the unit from the conductor and press and hold th...

Page 13: ...to expose the battery holder Replace the two AA batteries noting proper polarity Either Alkaline or Lithium batteries may be used We recommend that you replace both units batteries at the same time E...

Page 14: ...Do not use CHANCE Moisture Eater II wipes on any part of the Full Range ARVI as it will cause damage Abuse or misuse will damage the unit Store in a dry location do not drop and protect from jostling...

Page 15: ...bbell Incorporated Chance Full Range ARVI Operating Instructions Optional Accessories Indicator Tester PSC4033582 15 kV Bushing Adapter T4030428 15 kV 25 kV 35 kV Bushing Adapter T4030857 Elbow Adapte...

Page 16: ...e humidity range 5 to 95 Rh Recommended storage at 45 Rh 8 Rh Shock Testing per IEC 60068 2 27 Test Ea and guidance Shock Level 1 500 m s2 50g 11ms Half sine pulse 3 pulses Positive Negative each axis...

Page 17: ...________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________...

Page 18: ...hubbellpowersystems com PSP4033591 TD_09_114_E Rev A Hubbell has a policy of continuous product improvement Please visit hubbellpowersystems com to confirm current design specifications 2017 Hubbell...

Reviews: