 Full Range ARVI Operating Instructions

Operations for Overhead

Turn the Unit On:

1.  Momentarily depress the “Power Button” for approximately 2 seconds.

a.  Upon power-up, each LED will illuminate individually from the lowest voltage to the highest 

followed by the adjustable audible alarm. These tests verify the function of the LEDs, alarm, 
batteries, and internal circuitry.

b.  Following the adjustable audible alarm, the “PWR” LED will continuously flash. The unit is 

ready for use.

c.  Always install the unit on an appropriate length insulated Hot Stick.

Take a Reading:

2.   Install the supplied Shepherd Hook and place the unit in contact with the power line conductor. 

Minimum Approach Distances (MAD) should be adhered to at all times.

a.  Ensure that the green "PWR" LED is flashing before, during, and after testing.

b.  Keep the Full-Range ARVI perpendicular to the phase conductor and away from poles or 

structures a distance of at least twice the circuit’s phase spacing. If possible, test away from 
structures, jumpers, risers, cutouts, insulators, ground wires, and any system components that 
may cause reading errors.

c.  The audible alarm will begin to beep as the unit senses the electric field. The Range LED that 

corresponds with the system voltage level present on the conductor will begin to blink. The 
higher the voltage, the faster the beeping occurs. Audio and visual indications may begin 
before contact is made.

d.  Test three or four locations to check consistency. Where little or no consistency is apparent, 

consider the highest reading as correct.

e.  All interpretations should take into account the circuit configuration, length, proximity to 

other lines; and should be consistent with previous experience on the same circuit with 
this instrument. If ever in doubt about interpreting Full-Range ARVI readings under any 
circumstance, always assume circuit is energized and take appropriate safety precautions.

Hold Mode: 

Refer to page 14.

Turn the Unit Off:

3.  To turn the Full-Range ARVI off:

a.  Press and hold the "Power Button" on the unit for 3 seconds:

i.  The adjustable audible alarm will generate two series of three tones each.
ii.  The unit will turn off after the second series of tones.

b.  Or the unit will automatically power itself down (auto-off) after approximately 15 minutes of 

inactivity.

Summary of Contents for CHANCE PSC4032915

Page 1: ...evision A 02 17 Operating Instructions Model No PSC4032915 2017 Hubbell Incorporated hpsliterature hubbell com hubbellpowersystems com For use with Capacitive Test Point through 765 kV AC NOTICE Befor...

Page 2: ...dures techniques etc that if not followed carefully could RESULT IN DEATH A WARNING refers to operating procedures techniques etc that if not followed carefully could RESULT IN INJURIES OR DEATH A CAU...

Page 3: ...ered in relation to installation operation or maintenance Should additional information and details be desired or if situations arise which are not covered adequately for the user s purpose the specif...

Page 4: ...high If the universal coupling is too close to a jumper or equipment of the same phase the indication will tend to be low The tool must always be used with an appropriate length Hot Stick for safety...

Page 5: ...quivalent voltage ranges to provide indication of each of the Voltage Classes are as follows Voltage Class Voltage Range 600 V 480 V to 900 V 4 kV 1 kV to 6 5 kV 15 kV 6 6 kV to 17 kV 25 kV 18 kV to 2...

Page 6: ...sulators ground wires and any system components that may cause reading errors c The audible alarm will begin to beep as the unit senses the electric field The Range LED that corresponds with the syste...

Page 7: ...the electromagnetic action of current and electrostatic action of voltage can induce a high static condition on the de energized circuit Activity effects can exist between all conductor pairs The Ful...

Page 8: ...round equipment 1 When testing dead front URD equipment use an appropriate Bushing Adapter on the Bushing Well On Capacitive Test Points use the Straight Probe Never use the Shepherd Hook on URD equip...

Page 9: ...For live front install the small hex head machine screw 1 4 20 X 3 8 long Minimum Approach Distances MAD should be adhered to at all times a Ensure that the green PWR LED is flashing before during an...

Page 10: ...tive Test Points must be free of corrosion and contamination for valid testing 2 While observing all required safe work practices and with an appropriate length insulated Hot Stick attached to the Ful...

Page 11: ...ll the elbow with elbow puller tool then orient the elbow so it is safely accessible for testing 2 Utilizing all safe practices and procedures Operator 2 with the installed elbow adapter on the Full R...

Page 12: ...unit then will return to the normal audible mode but one LED will remain solid until reset To reset the unit after a held reading is displayed Remove the unit from the conductor and press and hold th...

Page 13: ...to expose the battery holder Replace the two AA batteries noting proper polarity Either Alkaline or Lithium batteries may be used We recommend that you replace both units batteries at the same time E...

Page 14: ...Do not use CHANCE Moisture Eater II wipes on any part of the Full Range ARVI as it will cause damage Abuse or misuse will damage the unit Store in a dry location do not drop and protect from jostling...

Page 15: ...bbell Incorporated Chance Full Range ARVI Operating Instructions Optional Accessories Indicator Tester PSC4033582 15 kV Bushing Adapter T4030428 15 kV 25 kV 35 kV Bushing Adapter T4030857 Elbow Adapte...

Page 16: ...e humidity range 5 to 95 Rh Recommended storage at 45 Rh 8 Rh Shock Testing per IEC 60068 2 27 Test Ea and guidance Shock Level 1 500 m s2 50g 11ms Half sine pulse 3 pulses Positive Negative each axis...

Page 17: ...________________________________________________________ ___________________________________________________________________________________ ___________________________________________________________...

Page 18: ...hubbellpowersystems com PSP4033591 TD_09_114_E Rev A Hubbell has a policy of continuous product improvement Please visit hubbellpowersystems com to confirm current design specifications 2017 Hubbell...

Reviews: