Figure 4-34. Alarm Configuration
1.
Major Alarm – Pickup Delay:
Once an abnormal condition is detected, as programmed
in the alarm configurations below, the pickup timer can be set to delay the major alarm
indication from 0 to 30 seconds in 125ms increments.
2.
Major Alarm – Dropout Delay:
Once an abnormal condition ceases, the dropout timer
can be set to delay the ending of the major alarm indication from 0 to 30 seconds in 125ms
increments.
3.
Minor Alarm – Pickup Delay:
Once an abnormal condition is detected, as programmed
in the alarm configurations below, the pickup timer can be set to delay the minor alarm
indication from 0 to 30 seconds in 125ms increments.
4.
Minor Alarm – Dropout Delay:
Once an abnormal condition ceases, the dropout timer
can be set to delay the ending of the minor alarm indication from 0 to 30 seconds in 125ms
increments.
5.
General System Alarms:
These alarms can be set to activate the HPS/RFL GARD Pro
system major alarm, minor alarm, both alarms (major and minor) and no alarms as
required.
6.
Internal Alarms:
Contact HPS/RFL Service before changing these settings, normally
for HPS/RFL service use only.