System Configuration __________________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
4-57
The HPS/RFL GARD Pro system can send the following list of data to the master computers:
Table 4-6. HPS/RFL GARD Pro system list of DNP3 data points
HPS/RFL GARD Pro system
DNP Objec
t
Notes
Normal
Change event
Source
Description
Labels
3
unit
s
Descripti
on
Type Var Type
Var
System
Logic
HMI input
HMI Input 0-63
n/a
Binary
output
10
2
11
1
50 ms
2
HMI output
HMI Output 0-63
n/a
Binary
input
1
1
2
1
50 ms
2
SOE
Counters
Counters of the SOE Triggers
n/a
32-bit
Binary
Counter
20
1
22
1
SOE
triggers
SOE triggers 0-191
n/a
Binary
input
1
1
2
2
1
1 ms
2
PLC
FSK
Analog
Values
Tx Power
Rx Level
Reflected Power
Signal-to-Noise Ratio
Trans Hybrid Loss
dBm
dB
%
dB
dB
32-bit
floating
point
30
1
32
1
Counters
Trip 1 Key
Trip 2 Key
Trip 1 Rx
Trip 2 Rx
Rx Alarm
Reflected Power Alarm
n/a
32-bit
Binary
20
1
22
1
Rollover
at 255
4
PLC
On/Off
Analog
Values
Tx Power
Rx Level
Reflected Power
SNR
dBm
dB
%
dB
32-bit
floating
point
30
1
32
1
Counters
Start 1
Start 2
Stop 1
Stop 2
Block Rx
Reserve Key
Checkback Tests Run
Checkback Tests Passed
Checkback Tests Failed
n/a
32-bit
Binary
20
1
22
1
Rollover
at 255
4
Note 1
: For change events, SOE Trigger points will be reported with timestamps synchronized
to the HPS/RFL GARD Pro system clock and as reported in the Sequence of Events report.
Note 2:
To be recorded as a DNP change event, the duration of the event must be a minimum of
1 millisecond for SOE Trigger points or 50 milliseconds for HMI Out and HMI In.
Note 3
: Functional Module Point labels can be configured through the appropriate DNP
configuration pages. To change the default labels for Functional Module Points, navigate to the
appropriate tabs on the Configuration > DNP >
point type pages
.
The System Logic Point labels can be changed in the appropriate Configuration > SOE and
Advanced > HMI pages.
Note 4
: Internally these counters are 8-bit and rollover at 255.