Digital Communications Interfaces ________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
7-30
14.
Errored Seconds
: Provides a count of the total number of errored seconds since the last
reset.
15.
Errors per Second
: Provides a count of the number of errored words that occurred over
the last second.
7.5.3 Status G.703 Digital Comms
This page allows the user to view the status of different parameters of the G.703 comms interface
module.
1
2
9
3
4
5
6
7
8
10
11
12
14
13
STATUS > Digital Comms > Slot # - G.703
Figure 7-22. Status Screen G.703 Digital Comms
1.
Service
: This value indicates if the module is enabled for service.
Range:
Settings to create this Status
Status Message
Enable
Module Mapping
“Forced Disabled” Disabled
“Aux Channel”
Aux Channel
“Enabled”
Auto
Any Bus/timeslot
“Disabled”
Auto
Not mapped to any Bus/timeslot
2.
# of Data Channels
: This value is an indication of how many timeslots the interface is
carrying. For G.703/64k this value will never be greater than 1.
If module is Disabled and Enable = Auto, field = “0”. If module is Forced Disabled,
field = “N/A”.