Page 2 of 3
3940 Dr. Martin Luther King Drive
St. Louis, MO 63113
KIL00921465 FORM NO. K1465 06/15 ERO-8-029-15
For Class I, Division 2, Groups A, B, C & D
Class II, Division 1, Groups E, F & G; Class III.
Type 3 and 4. IP66. Operating Temperature Range
-50°C +60°C
1.
Back Nut
2. Middle Nut
3. Grounding Spring (Captive in the Middle Nut)
4. Armor Stop
5. Elbow
6. Locking Collar
7. Potting Chamber
8. Entry Component
9. O-Ring (Captive in Entry Component)
ASSEMBLY INSTRUCTIONS
STEP A
(Refer to Figure A on left)
Strip cable to suit equipment as shown above,
exposing metal armor sheath (I) and insulated
cores (II).
I
= 3/4” (19mm) for ½” size glands
I
= 13/16” (21mm) for ¾” size glands
I
= 1” (25mm) for 1” size glands
I
= 1-1/4” (32mm) for1-¼” size glands
II
to suit equipment
STEP B
(Refer to Figure B on left)
Push the cable through the back nut (1), middle
nut (2), and grounding spring (3). Locate the armor
stop (4) at the end of the armor as shown below. If
the conductors are too large to fit through the armor
stop (4) it can be removed from the assembly. The
elbow component (5) has a built in armor stop for
larger cables. Feed the wires through the elbow
and tighten the middle nut (2) and backnut (1) to
the torque shown in Table A (Approximately hand
tight + 1 turn). This will compress the grounding
spring (3) to grip the armor for grounding.
Figure A
Figure B