INSTALLATION, OPERATION & 

MAINTENANCE DATA SHEET 

SERIES SJIC and SJICH JUNCTION BOXES 

Increased Safety Terminal Enclosures For Use In 

Zone Classified Hazardous Locations

 

 

P/N KIL00921446 FORM NO. K1446  R6/18  ECO-2-045-18   
 

 

 

 

Page 1 of 

10

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
* - Suitable For Use In Division Classified 
Locations Based On Equivalency - See North 
American Certification Ratings Below 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

   

 

 

General Safety Information:

 

CAUTION

:

 

Before installing, make sure you are compliant with area classifications, failure to do so may result in bodily injury, death and 
property damage. Do not attempt installation until you are familiar with the following procedures. All installation must comply with 
the applicable Electrical Code. 

Make sure that the circuit is De-energized before starting installation or maintenance.   
Verify that the installation is grounded.  Failure to ground will create electrical shock hazards, which can cause serious injury and or 
death.

 

IMPORTANT: 

  

Please read these instructions carefully before installing or maintaining this equipment. Good electrical practices should be followed 
at all times and this data should be used as a guide only.

 

Technical information, advice and recommendations contained in these documents is based upon information that Killark believes to be reliable. 
All the information and advice contained in these documents is intended for use only by persons having been trained and possessing the requisite 
skill and know-how and to be used by such persons only at their own discretion and risk. The nature of these instructions is informative only and 
does not cover all of the details, variations or combinations in which this equipment may be used, its storage, delivery, installation, check out, safe 
operation and maintenance.  Since conditions of use of the product are outside of the care, custody and control of Killark, the purchaser should 
determine the suitability of the product for his intended use, and assumes all risk and liability whatsoever in connection therewith.

 

         

                 

SERIES SJIC and SJICH JUNCTION BOXES 

Increased Safety Terminal Enclosures For Use In 

Zone* Classified Hazardous Locations

 

 

0518

 

SIRA 14 ATEX 3157 

IECEx SIR 14.0054

 

Summary of Contents for Killark SJIC

Page 1: ... or death IMPORTANT Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a guide only Technical information advice and recommendations contained in these documents is based upon information that Killark believes to be reliable All the information and advice contained in the...

Page 2: ...ked ambient on the nameplate e A 1 4 20 UNC M6 ground earthing stud is supplied on all Series SJICH and SJICH stainless steel enclosures f To maintian proper IP ratings be sure to follow all mfr s mounting instructions when installing certified cable glands or conduit entries Warning Enclosures must be installed in the upright vertical position only Mounting the enclosures in a horizontal position...

Page 3: ...ed etc per EN 60079 7 The operating service temperature of the enclosure is limited to the temperature of the gland fitting if less than the enclosure h Killark KDE series drain and breather may be installed The operating temperature of the enclosure is limited to the temperature of the drain and breathers if lower than the enclosure s Other drain and breathers may be installed the user is respons...

Page 4: ...ll be suitable for exceed the minimum ambient and maximum temperature defer to T Code achieved in service All conductors shall be sized per the National or Local Electrical Codes for the max continuous current or max motor load of the installation h Conductors at entry points may reach 73o C in a 55o C ambient and may reach 108o C in a 90o C ambient See Note j below i Only the terminal blocks list...

Page 5: ...52U IECEx FTZU 10 0011U 50o C Klemsan Elektrik PUK Screw FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C Klemsan Elektrik PYK Cage clamp FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C ABB ZS Screw LCIE 08ATEX0007U IECEx LCI 08 0031U 50o C ABB ZK Cage clamp LCIE 13ATEX3042U IECEx LCI 13 0025U 50o C WAGO 2001 Cage clamp PTB 05ATEX1094U IECEx PTB 11 0093U 50o C WAGO 2002 Cage clamp PTB 03ATEX1162U IECEx PTB 0...

Page 6: ...9 7 ANSI ISA 60079 7 CSA 60079 31 ANSI ISA 60079 31 CSA No 94 1 94 2 No 14 UL50 UL50E UL508 CSA 60529 ANSI IEC 60529 IEC ATEX Certifications ATEX Ratings SIRA 14 ATEX 3157 0518 II 1 G Ex ia IIC T6 T5 T4 Ga II 2 D Ex tb IIIC T80o C T100o C T130o C Db IP66 OR 0518 II 2 G Ex eb IIC T6 T5 T4 Gb Ex ib IIC T6 T5 T4 Gb II 2 D Ex tb IIIC T80o C T100o C T130o C Db IP66 OR 0518 II 1 G Ex eb ib IIC T6 T5 T4 ...

Page 7: ...onnection must be made in all circumstances Conduit Hubs and Cable Glands Conduit hubs and cable gland sizes may be mixed The maximum number of hubs or cable glands must be selected such that the walls are not weakened nor the enclosure stability affected See Figure 1 and 2 below and Tables 1 7 below for metal enclosure dimensions and mounting hole locations conduit and gland mountnig details usea...

Page 8: ... 75 121 2 47 63 3 13 79 3 13 79 1 19 30 SJIC 060404 6 152 4 102 4 102 2 00 51 6 75 171 2 47 63 5 13 130 3 13 79 3 19 81 SJIC 060604 6 152 6 152 4 102 4 00 102 6 75 171 2 47 63 5 13 130 5 13 130 3 19 81 SJIC 060606 6 152 6 152 6 152 4 00 102 6 75 171 4 47 114 5 13 130 5 13 130 3 19 81 SJIC 080606 8 203 6 152 6 152 4 00 102 8 75 222 4 47 114 7 13 181 7 13 181 5 19 132 SJIC 080804 8 203 8 203 4 102 6...

Page 9: ... Blank Wall Area D Blank Wall Area E Blank Wall Area SJICH 060604 6 152 6 152 4 102 4 00 102 6 75 171 2 47 63 5 13 130 5 13 130 3 19 81 1 81 46 SJICH 060606 6 152 6 152 6 152 4 00 102 6 75 171 4 47 114 5 13 130 5 13 130 3 19 81 3 81 97 SJICH 080606 8 203 6 152 6 152 4 00 102 8 75 222 4 47 114 7 13 181 7 13 181 5 19 132 3 81 97 SJICH 080804 8 203 8 203 4 102 6 00 152 8 75 222 2 47 63 7 13 181 7 13 ...

Page 10: ...BLE 7 Minimum Distance From Center Line to Center Line of Conduit Cable Entries NPT Metric 4 3 1 2 3 M75 2 1 2 M63 2 M50 1 1 2 M40 1 1 4 M32 1 M25 3 4 M20 1 2 M16 IN mm 2 3 4 70 2 1 2 64 2 51 2 51 1 5 8 41 1 3 8 35 1 1 4 32 1 25 7 8 22 3 4 19 NPT Metric 4 3 1 2 3 M75 2 1 2 M63 2 M50 1 1 2 M40 1 1 4 M32 1 M25 3 4 M20 1 2 M16 IN mm 3 1 4 83 3 76 2 3 4 70 2 1 2 64 2 1 8 54 1 7 8 48 1 3 4 44 1 1 2 38 ...