background image

 

HUBBELL ELECTRICAL PRODUCTS 

A Division of HUBBELL INCORPORATED (Delaware) 
3940 Dr. Martin Luther King Drive 
St. Louis, Missouri  63113 USA 

INSTALLATION, OPERATION & 

MAINTENANCE DATA SHEET 

SERIES  USF JUNCTION BOXES 

Increased Safety Terminal Enclosures For Use In 

Zone Classified Hazardous Locations

 

 

P/N KIL00921445 FORM NO. K1445  R6/18  ECO-2-045-18   
 

 

 

 

Page 3 of 

10

 

Enclosure and Cover Installation Instructions 

 

WARNING: Enclosures that are powder coated have a potential electrostatic charging hazard. Wipe the enclosure down with a moist cloth 
before servicing. 

a: 

 Using a screwdriver with a #2 Phillips Head, a Standard Slotted or Robertson style head, remove the cover screws.  Securely fasten the 

enclosure to the mounting location, using up to a  

1/4” (M6)  

diameter steel bolt and washer.   The mounting location must be flat and provide 

proper clearance, rigidity and strength to support the enclosure and all contained devices.  Mounting dimensions are shown in this document.   

b: 

  Install Internal Components per the Mfrs. installation instructions.  (See

 "Wiring and Terminal Block" 

and

 "Cable Gland / Conduit Entry" 

Installation Instructions

  Sections below). 

c:

  Grounding connections are available at the din rail, earth continuity plate and internal- external ground stud.   

d:

  Bonding connections are available on covers and boxes of all enclosures.  All exposed metal should be bonded per  local electrical codes. 

e: 

 Closing / Installing the enclosure cover: Thread each cover screw half way into the threaded insert without completely tightening in a diagonal 

pattern. Then complete installation of cover by tightening screws in the same diagonal pattern to a minimum torque of 3 Nm (26 lb-ins.) to a 
maximum of 4 Nm (35 lb-ins.).  

DO NOT OVERTIGHTEN OR USE AN IMPACT TOOL.  A consistent fit over the entire length of the cover joint 

should be verified at the time of installation. 

f: 

 This enclosure is provided without cable glands / conduit sealing devices.  Proper selection of cable glands / conduit sealing devices must 

occur in the field.    

 

g: 

 Cable fittings must be certified “Ex e” components per EN 60079-7. For lines which are not permanently installed, only cable fittings 

appropriate for this purpose can be used. They are to be protected from loosening and locked against rotation, i.e. clips, cemented, etc., per EN 
60079-7. The operating (service) temperature of the enclosure is limited to the temperature of the gland fitting if less than the enclosure

.  

h: 

 Killark KDE series drain and breather may be installed. The operating temperature of the enclosure is limited to the temperature of the drain 

and breathers if lower than the enclosure's. 

Other drain and breathers may be installed, the user is responsible for ensuring that the 

protection concept, temperature class and relevant IP rating is maintained.  

i:

  All unused conduit openings must be fitted with a certified close-up plug of equivalent minimum required IP rating as required.

 

Terminal  Block  Installation and  Wiring Instructions:   

 

a: 

  Attention to detail is highly recommended when installing and wiring the Terminal Blocks.   Proper installation is required to ensure the 

component Certification Ratings are not invalidated.  

b:  

Care should be taken not to damage or crack the DIN-Rail mounting clips when removing or installing polymeric terminal blocks.  

Damaged or 

loose-fitting  terminal blocks should be replaced before energizing the device.

   

c:

  Refer to each Terminal Block Manufacturer's  Installation Instructions for suitable wire types (ie: Solid, Stranded), proper wire stripping lengths, 

and terminal torques.  

OVERTIGHTENED  or 

 

LOOSE WIRE  TERMINALS  MAY  CAUSE   OVERHEATING,   WHICH  CAN  RESULT  IN  AN  

ELECTRIC  SHOCK  OR  EXPLOSION  HAZARD

d

  Care shall be taken to ensure proper separation of circuits (voltages), and spacings (creepage and clearance distances between live parts of 

opposite polarity, and between all live parts and dead metal) are maintained.  Refer to IEC/EN/UL/CSA 60079-7, Table 2, for minimum creepage 
and clearance distances. 

e:

  Grounding connections are available at the din rail, earth continuity plate and internal- external ground stud.  Bonding connections are 

available on covers and boxes of all enclosures.  All exposed metal should be bonded per  local electrical codes. 

f:

  Wiring must be carried out in accordance with the relevant local and national electrical codes (ie: IEC/EN 60079-14, IEC/EN 61241-0 and 

IEC/EN 61241-1. 

g:

  

All conductor insulation and terminal block service temperature ratings shall be suitable for (exceed)  the minimum ambient and 

maximum temperature (defer to T-Code) achieved in service.   All conductors shall be sized per the National or Local  Electrical  Codes 
for the max. continuous current or max. motor load of the installation. 

h:

  C

onductors at entry points may reach 73

o

C in a +55

o

C ambient, and may reach 108

o

C in a +90

o

C ambient.    

i

:

  Only the terminal blocks listed on Killark certificates  may be installed in the enclosures. See 

Table A

 below. 

j:

  No more than one conductor shall not be permitted in a wire terminal, unless the device has been evaluated specifially for  multiconductor 

installation  (See Terminal Block Mfr's Installation Instructions).   Ferrules may be used if the Terminal Block has been approved for use with Solid 
Wires of equivalent diameter. 

k:

  When installing Terminal blocks,  the maximum voltage, current and dissipated power shown on the Junction Box nameplate must not be 

exceeded. 

l:

   When Weidmuller 

WDU 1.5 or WDU 2.5

 Series Terminal Blocks are installed, they are limited to a 

maximum current of 15A

.

 

Summary of Contents for Killark USF Series

Page 1: ...or death IMPORTANT Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a...

Page 2: ...ng in accordance with the local jurisdictional electrical code s e A 1 4 20 UNC M6 ground earthing stud is supplied on all Series USF enclosures f To maintian proper IP ratings be sure to follow all m...

Page 3: ...nstalled the user is responsible for ensuring that the protection concept temperature class and relevant IP rating is maintained i All unused conduit openings must be fitted with a certified close up...

Page 4: ...IECEx FTZU 10 0011U 50o C Klemsan Elektrik PUK Screw FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C Klemsan Elektrik PYK Cage clamp FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C ABB ZS Screw LCIE 08ATEX0007...

Page 5: ...must seat fully against each other to provide the proper joint d Apply a light coating of Killark LUBG lubricant to the box flange before closing the cover All cover screws must be installed tightly 2...

Page 6: ...IIC T6 T5 T4 Gb with Ex e terminals only OR Ex ib IIC T6 T5 T4 Gb with Ex ib terminals only Ex tb IIIC T80o C T100o C T130o C Db IP66 OR Ex eb ib IIC T6 T5 T4 Gb with Ex e ib terminals Ex tb IIIC T80o...

Page 7: ...inimum Distance From Center Line to Center Line of Conduit Cable Entries NPT Metric 4 3 1 2 3 M75 2 1 2 M63 2 M50 1 1 2 M40 1 1 4 M32 1 M25 3 4 M20 1 2 M16 IN mm 2 3 4 70 2 1 2 64 2 51 2 51 1 5 8 41 1...

Page 8: ...ed Hazardous Locations P N KIL00921445 FORM NO K1445 R6 18 ECO 2 045 18 Page 8 of 10 FIGURE 1 USF HINGED COVER See Table 6 and 7 below Note The maximum hole size for enclosure depths of 6 153mm throug...

Page 9: ...69 576 17 63 448 25 63 651 23 0 11 5 USF241608 24 610 16 407 8 203 18 69 475 18 69 475 21 63 549 21 63 549 23 0 11 5 USF241610 24 610 16 407 10 254 14 69 373 22 69 576 17 63 448 25 63 651 31 0 15 5 US...

Page 10: ...4 19 2 488 USF241606 11 79 299 19 20 488 5 79 147 11 75 298 35 2 894 11 2 284 USF241608 11 79 299 19 20 488 11 79 299 11 75 298 35 2 894 15 2 386 USF241610 7 79 198 23 20 589 7 79 198 11 75 298 35 2 8...

Reviews: