background image

 

HUBBELL ELECTRICAL PRODUCTS 

A Division of HUBBELL INCORPORATED (Delaware) 
3940 Dr. Martin Luther King Drive 
St. Louis, Missouri  63113 USA 

INSTALLATION, OPERATION & 

MAINTENANCE DATA SHEET 

SERIES  USF JUNCTION BOXES 

Increased Safety Terminal Enclosures For Use In 

Zone Classified Hazardous Locations

 

 

P/N KIL00921445 FORM NO. K1445  R6/18  ECO-2-045-18   
 

 

 

 

Page 6 of 

10

 

Certification Information

 

North American  Certifications:         

North American (NEC/CEC) Certifications***: 

Class I, Zone 1  AEx eb IIC Gb   T6...T4    (U.S.) 
Zone 21 AEx tb IIIC Db  T80

 o

C...T130

 o

C   IP66    (U.S.) 

Ex db eb IIC Gb  T6...T4     (CAN) 
Ex tb IIIC Db  T85

 o

C...T135

 o

C   IP66    (CAN) 

Class I, Division 2, Groups A,B,C,D 
Class II, Zone 21 & 22 
Class II, Groups E, F, G;   Class III 
Type 3/4/4X**/IP66 
** - Only 304 and 316 Stainless Steel Enclosures are Type 4X 
 
- 50

o

≤ Ta ≤ +40

o

C  (when marked T6 / T80

o

C) 

- 50

o

≤ Ta ≤ +55

o

C  (when marked T5 / T100

o

C) 

- 50

o

≤ Ta ≤ +90

o

C  (when marked T4 / T130

o

C) 

 

Standards Applied: 
CSA 60079-0                        ANSI/ISA 60079-0 
CSA 60079-7                       ANSI/ISA 60079-7 
CSA 60079-31                     ANSI/ISA 60079-31 
CSA No. 94.1 / 94.2 / 14      UL50 / UL50E / UL508 
CSA 60529                          ANSI/IEC 60529 

 

 

 

IEC / ATEX Certifications: 

 
ATEX  Ratings

:  SIRA 14 ATEX 3157   

0518

 II 1 G  Ex ia IIC T6/T5/T4  Ga     

II 2 D  Ex tb IIIC T80

o

C / T100

o

C / T130

o

C  Db  IP66 

OR 

0518

 II 2 G  Ex eb IIC  T6/T5/T4  Gb   

Ex ib IIC  T6/T5/T4  Gb       
II 2 D  Ex tb IIIC T80

o

C / T100

o

C / T130

o

C  Db  IP66 

OR 

0518

 II 1 G  Ex eb ib IIC T6/T5/T4  Gb     

II 2 D  Ex tb IIIC T80

o

C / T100

o

C / T130

o

C  Db  IP66

 

 
IECEx  Ratings

:   IECEx SIR 14.0054 

When ia Terminals are installed (only): 

Ex ia IIC T6/T5/T4  Ga     
Ex tb IIIC T80

o

C / T100

o

C / T130

o

C  Db  IP66 

OR 

Ex eb IIC  T6/T5/T4  Gb  

(with Ex e terminals only

)   OR 

Ex ib IIC  T6/T5/T4  Gb  

(with Ex ib terminals only

)        

Ex tb IIIC T80

o

C / T100

o

C / T130

o

C  Db  IP66 

OR 

Ex eb ib  IIC  T6/T5/T4  Gb   

(with Ex e & ib terminals

)    

Ex tb IIIC T80

o

C / T100

o

C / T130

o

C  Db  IP66 

 

#

o

≤ Ta ≤ +40

o

C  (when marked T6 / T80

o

C) 

#

o

≤ Ta ≤ +55

o

C  (when marked T5 / T100

o

C) 

#

o

≤ Ta ≤ +90

o

C  (when marked T4 / T130

o

C) 

 

#

 - Mimumum Ambient Temp. may be either -50

o

C, -45

o

C, -40

o

C or -20

o

C - See Table 

1 below for minimum ambient ratings based on installed T-Blocks. 
 

Standards Applied: 
EN 60079-0          IEC 60079-0 
EN 60079-7          IEC 60079-7 
EN 60079-11        IEC 60079-11    (Terminal Blocks) 
IEC 60079-31

 

 Electrical Ratings  

 

The overall electrical ratings of an USF Junction Box is dependent upon the ratings of the terminal blocks installed.  

Please refer to the Terminal 

Block Mfr's. website - or see the Killark Online Catalog (Section E) for specific Terminal Block Current, Voltage and Resistance (Full and 
Partial Load Wattage) ratings:

 

http://ecatalog.hubbell-killark.com/

 

Labels / Nameplates

 

To maintain the IP (Ingress Protection)  levels and the NEMA / TYPE ratings of the Series USF enclosures, end-product nameplates or label & tag 
mounting holes must 

not penetrate the interior of the enclosure.

 

 

Earthing (Grounding) 

The earth connection accepts a cable lug. The cable must be run and fixed near to the enclosure.  The earth connection must be made in all 
circumstances. 
 

Conduit Hubs and Cable Glands 

Conduit hubs and cable gland sizes may be mixed.  The maximum number of hubs or cable glands must be selected such that the walls are not weakened 
nor the enclosure stability affected . 
 
See Figure 1 below, and Tables 1 - 7  below for Enclosure Dimensions and Mounting Hole Locations,  Conduit and Gland Mountnig Details (Useable Wall 
Area, Hole Spacing Details, etc) . 

 

Summary of Contents for Killark USF Series

Page 1: ...or death IMPORTANT Please read these instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a...

Page 2: ...ng in accordance with the local jurisdictional electrical code s e A 1 4 20 UNC M6 ground earthing stud is supplied on all Series USF enclosures f To maintian proper IP ratings be sure to follow all m...

Page 3: ...nstalled the user is responsible for ensuring that the protection concept temperature class and relevant IP rating is maintained i All unused conduit openings must be fitted with a certified close up...

Page 4: ...IECEx FTZU 10 0011U 50o C Klemsan Elektrik PUK Screw FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C Klemsan Elektrik PYK Cage clamp FTZU 09ATEX0252U IECEx FTZU 10 0011U 50o C ABB ZS Screw LCIE 08ATEX0007...

Page 5: ...must seat fully against each other to provide the proper joint d Apply a light coating of Killark LUBG lubricant to the box flange before closing the cover All cover screws must be installed tightly 2...

Page 6: ...IIC T6 T5 T4 Gb with Ex e terminals only OR Ex ib IIC T6 T5 T4 Gb with Ex ib terminals only Ex tb IIIC T80o C T100o C T130o C Db IP66 OR Ex eb ib IIC T6 T5 T4 Gb with Ex e ib terminals Ex tb IIIC T80o...

Page 7: ...inimum Distance From Center Line to Center Line of Conduit Cable Entries NPT Metric 4 3 1 2 3 M75 2 1 2 M63 2 M50 1 1 2 M40 1 1 4 M32 1 M25 3 4 M20 1 2 M16 IN mm 2 3 4 70 2 1 2 64 2 51 2 51 1 5 8 41 1...

Page 8: ...ed Hazardous Locations P N KIL00921445 FORM NO K1445 R6 18 ECO 2 045 18 Page 8 of 10 FIGURE 1 USF HINGED COVER See Table 6 and 7 below Note The maximum hole size for enclosure depths of 6 153mm throug...

Page 9: ...69 576 17 63 448 25 63 651 23 0 11 5 USF241608 24 610 16 407 8 203 18 69 475 18 69 475 21 63 549 21 63 549 23 0 11 5 USF241610 24 610 16 407 10 254 14 69 373 22 69 576 17 63 448 25 63 651 31 0 15 5 US...

Page 10: ...4 19 2 488 USF241606 11 79 299 19 20 488 5 79 147 11 75 298 35 2 894 11 2 284 USF241608 11 79 299 19 20 488 11 79 299 11 75 298 35 2 894 15 2 386 USF241610 7 79 198 23 20 589 7 79 198 11 75 298 35 2 8...