INSTALLATION, OPERATION &  

MAINTENANCE DATA SHEET 

 

SERIES VSIH                

ATTACHMENT PLUGS 

 

 

P/N KIL00921520  FORM NO. K1520  R07/21  ECO-7-012-21

 

 

 

 

 

 

 

 

Page 

3

 of 

7

 

 

 

Example Plug Marking Labels - ATEX / IECEx:   

 
 

 

 
 
 
 

THIS DOCUMENT SHOULD BE READ CAREFULLY BEFORE INSTALLATION 

 

1. 

INSTALLATION , OPERATION AND MAINTENANCE INSTRUCTIONS FOR SAFE USE

 

 
1.1  SAFETY RULES 
 
VSIH SERIES sockets (receptacles) are designed as Group II Category 2 equipment suitable for use in fixed 
installations in Classifed Hazardous Location areas designated Zone 1/21 and Zone 2/22. 
 
These operating instructions must be kept in a safe place for future reference.  Use VHIS Series devices only as 
intended and in undamaged / clean condition, and only where the resistance of the material to the surroundings 
is assured.  NO modifications are allowed to Series VHIS devices which are not specifically described in this 
instruction manual.  When installing Series VHIS devices, the creepage and clearance distances shall be duly 
considered as noted in Item 5.3, Table 8 below.   
 
Series VSIH Plugs are available in materials GRP with the following rated current 16A, 32A, 63A and 125A. 
 
Series VSIH Plugs are intended to be used with Series VSIH Sockets (Receptacles) rated Ex db eb IIC / Ex tb 
IIIC.  The Series VSIH socket switch handle controls a mechanical interlock mechanism which keeps the plug 
from being separated from the socket outlet while the contacts are energized.  The plug can only be removed 
from the socket (receptacle) when the switch handle is in postion 0 (zero). 
 
1.2  CONFORMITY TO STANDARDS 
 
Series VSIH devices have been evaluated and Certified to the following Standards**: 

IEC/EN 60079-0, -7, -31

;      

IEC/EN 60309-1, -2

 

** - refer to the IECEx and ATEX Certificates for the current editions of each Standard. 

 

 

 

 

 

Summary of Contents for KILLARK VSIH Series

Page 1: ...hese instructions carefully before installing or maintaining this equipment Good electrical practices should be followed at all times and this data should be used as a guide only Technical information...

Page 2: ...rk A Division of Hubbell Inc Delaware 2112 Fenton Logistics Park Blvd Fenton Missouri 63026 USA INSTALLATION OPERATION MAINTENANCE DATA SHEET SERIES VSIH ATTACHMENT PLUGS P N KIL00921520 FORM NO K1520...

Page 3: ...nce of the material to the surroundings is assured NO modifications are allowed to Series VHIS devices which are not specifically described in this instruction manual When installing Series VHIS devic...

Page 4: ...mbient temperature is 60oC Tcable 90oC for Series VSIH63 when max ambient temperature is 60oC Tcable 85oC for Series VSIH125 2 2 TYPES OF PROTECTION ATEX Certificate INERIS 20 ATEX 0022X IECEx Certifi...

Page 5: ...k 125P405 50 60 380 440 Red 3 20R403 32R403 63R403 Black 125R403 3P E 100 300 50 690 Red 10 20P410 32P410 63P410 Black 125P410 3P E 300 500 50 690 Red 2 20P402 32P402 63P402 Black 125P402 3P N E 50 60...

Page 6: ...the warranty provision No changes to the plug impairing its explosion protection are permitted Install and operate the plug only if it is clean and undamaged 5 2 ACCESSORIES Protection Cup Only approv...

Page 7: ...NG 6 1 ROUTINE MAINTENANCE Routine maintenance is required to guarantee the efficiency of the enclosure and to maintain the required level of protection 1 Check that the sealing ring is in place and n...