UVPP and UVPPM Universal Voltage Power Packs
Installation Instructions

Hubbell Building Automation, Inc.

9601 Dessau Road • Building One • Suite 100 • Austin, Texas 78754  
512-450-1100 • 512-450-1215 Fax • www.hubbell-automation.com

Specifi cations

• 

Input:  100 to 277VAC, 50/60Hz

• 

Output:  24VDC, 150mA (Class 2), short circuit protected

• 

Relay Contacts:  20A, 120VAC Incandescent

20A, 120 or 277VAC Ballast
1HP, 120 or 277VAC Motor Load

• 

Internally Isolated Power Supply

• 

Zero Arc Point Switching

• 

Mounts inside or outside junction box, or inside fl uorescent ballast cavity

• 

Available with exclusive QTI (Quick-To-Install) system (UVPP version)

• 

Manual ON/OFF Support (UVPPM version) 

• 

Powers up to 4 sensors

• 

Plenum rated

• 

UL and cUL Listed

• 

5 year warranty

Precautions

• 

CAUTION:

  

RISK OF ELECTRICAL SHOCK.

  

Turn power off at service panel before beginning installation.

Never wire energized electrical components.

• 

Read and understand all instructions before beginning installation.

• 

NOTICE:

  For installation by a licensed electrician in accordance with National and/or local Electrical Codes and the 

following instructions.

• 

NOTICE:

  For indoor use only.

• 

CAUTION:

  

USE COPPER CONDUCTOR ONLY.

• 

Confi rm that device ratings are suitable for application prior to installation.

• 

NOTICE:

  Do not install if any damage to product is noticed.

UVPP Installation

1.  Turn power off at the service panel.
2.  Mount unit in installation site.  See Mounting  Diagram below.  Use 6x32 pan head screws to secure unit if mounting 

inside junction box or in lighting fi xture ballast cavity.  A Low Voltage Nipple Adapter (sold separately) is available for 
installing unit between two junction box knockouts.

3.  Electrically connect the unit to the circuit as shown in the Wiring Diagram below.  

4.  Reapply power at service panel. 

Mounts inside standard 4x4 

junction box

Mounts outside junction box 

via 1/2” EMT threaded nipple

Mounts inside fi xture ballast cavity

150mA)