 INSTRUCTION MANUAL ROOM CLIMATE CONTROL DEVICE 

 

GS 10.00 PRO 

HUGO MÜLLER GMBH & CO KG, STURMBÜHLSTR. 145-149, 78054 VS-SCHWENNINGEN

 

SAFETY INSTRUCTIONS AND BASICS 

 

 

 

 

Technical data / Connection diagram 

 

Safety instructions 

 

 

 

 

Power supply: 

Connect as stated on the product! 

 

 

CAUTION!

  

 

DANGER OF LIFE / RISK OF FIRE AND ELECTRIC SHOCK! 

!!!Installation and assembly of electrical equipment must be carried out only by a skilled person!!!

 

!!!For devices with 24V ACDC 

supply voltage following applies: 

SELV 

 

Channels (potential-free): 

4 switching channels, normally open 

 

 Connect the supply voltage/frequency as stated on the product! 

 

 Disconnect device from power supply for wiring and installation purposes! Check power supply is disconnected! 
 After completing the installation the terminal cover MUST be reattached! The device may only be operated with front and terminal cover! 
 The safety precautions of DIN VDE 0100, electric shock, and fire danger have to be met. 
 Defective devices / sensors have to be put out of service immediately! 
 For devices with 24V ACDC supply voltage following applies: The supply voltage must meet the requirements for SELV! 
 Installation and assembly of electrical equipment must be in accordance with local building and electrical codes! 

 Warranty void if housing opened by unauthorised person! 
  Do not use the sensor for safety-relevant gas measurements! 

Switching capacity: 

Connect as stated on the product! 

 

Analogue control outputs: 

3 x 0-10 Volt 

 

Permitted ambient temperature: 

0°…+50°C 

Housing: 

self-extinguishing thermoplastic 

Mounting: 

wall mounting 

 

Type of connection: 

Screw terminals 

Type of protection: 

IP 20 to DIN EN 60529 

Class of protection: 

II when installed according to regulations 

Features of actions: 

1B 

 

Usage / disposal 

 The climate control device is provided for use in interior and living areas! 

 The device includes sensors for measuring and controlling CO

2

 concentration, relative humidity and temperature.    

 

The relay switches in according to the set threshold values for CO

2

 and relative humidity (example for application: ventilation). Via  

 analogue control outputs the measured values of the CO

2

 concentration, relative humidity and temperature can be output. 

 The device is to be disposed in an environment-friendly way and according to current law.

 

 

 

 

   

 

ASSEMBLY

 

 

Assembly 

 

 

Disconnect device from power supply for wiring and installation  

      purposes! Check power supply is disconnected!

 

  Attention! You have to check and consider the safety instructions above! 

  This device is suitable for wall mounting or for mounting on a flush-mounting box. 

  The device should not be exposed to air draught or direct sunlight.  

 

Don´t install it curtains, or in niches, or close to heat sources. 

  The device should not be exposed to dusty environment. 

  Ensure that no dust get inside of this device. 

  For devices with 24V ACDC supply voltage following applies: 

 

The supply voltage must meet the requirements for SELV! 

  After initial startup, the device requires up to 5 minutes until the first correct 

 

measurement is possible 

 

 

 

Installation note: 

For an easy mounting and installation you can unplug the ribbon cable to remove the front cover completely. (Ribbon cable: logic cable connection 

between front-cover and back-cover). After mounting / installation => For a proper function of the device you have to reconnect in the ribbon cable. 

STEP 1:

  

Open the device at the bottom and remove the front cover!

 

STEP 2:

  

Remove the terminal cover (shown in grey)!

 

STEP 3:

  

Mount the rear cover to the wall or on a flush-mounting box(consider STEP 4)!

 

STEP 4:

  

Feed the cables through the appropriate cable passages: 

 

 

 

Cable passage 

I

:

 Cables for analogue outputs and GND (Terminal 1,2,3,4) 

 

 

 

Cable passage

 II

:

 Cables for Relay A and Relay B (Terminal 5,6 / 7,8) 

 

 

 

 

Cable passage

 III

Cables for Relay C and Relay d (Terminal 9,10 / 11,12) 

 

 

 

Cable passage

 IV

:

 Cables of the supply voltage (Terminal 13,14,15)

 

STEP 5:

  

After completing the installation the terminal cover MUST be reattached!

 

STEP 6:

  

Reattach the front cover!

 

 

 

 

OPERATION 

 

Settings and functions 

Functions 

(examine) 

Relay  Sensors 

Threshold 

settings  

Setting range 

(thresholds)

 

Response to the set 

thresholds 

Permanent switching 

Factory 

setting 

CO

concentration 

Relay 

CO

2

 [ppm] 

Via 

Rotary switch 

700ppm - 1.300ppm 

(± 100 ppm)

 

The relay switches on when 

exceeding the threshold 

(Hysteresis ± 50 ppm) 

Turn rotary switch  to  left end of scale (Pos. MIN): PERM ON 

Turn rotary switch  to  right end of scale (Pos. MAX): PERM OFF 

1.000ppm 

CO

concentration 

Relay 

CO

2

 [ppm] 

No settings possible! 

Fix

 

threshold 1400 ppm! 

The relay switches on when 

exceeding 1400 ppm 

(Hysteresis ± 50 ppm) 

No settings possible! 

Humidify 

Relay 

RH [%] 

Via 

Rotary switch  

15%RH - 45%RH 

(± 3%RH) 

The relay switches on when 

exceeding the threshold 

(Hysteresis ± 3%RH) 

Turn rotary switch  to  left end of scale (Pos. MIN): PERM  ON 

Turn rotary switch  to  right end of scale (Pos. MAX): PERM  OFF 

 

PERM 

OFF 

Dehumidify 

Relay 

RH [%] 

Via 

Rotary switch  

50%RH - 80%RH 

(± 3%RH) 

The relay switches on when 

exceeding the threshold 

(Hysteresis ± 3%RH) 

Turn rotary switch  to  left end of scale (Pos. MIN): PERM  OFF 

Turn rotary switch  to  right end of scale (Pos. MAX): PERM  ON 

65%RH 

 

LED-display – Relay status 

 

 

LED-DISPLAY 

OFF 

LED- DISPLAY 

PERMANENT GREEN 

LED- DISPLAY 

FLASHING GREEN 

LED- DISPLAY 

PERMANENT ORANGE 

CO

2

-LED

 

Relay A „OFF“ 
Relay B „OFF“ 

Relay A „OFF“ 
Relay B „OFF“ 

Relay A „ON“ 

Relay A and/or Relay B „ON“

 

Permanent OFF setting via rotary switch 

(setting via rotary switch A)

 

Measured value is below threshold 

(setting via rotary switch A) 

Measured value is above threshold  

(setting via rotary switch A)

 

Measured value over 1400 ppm or   

Permanent ON  setting via rotary switch  

(setting via rotary switch A)

 

 

CO

concentration OK 

CO

concentration above threshold 

CO

concentration poor 

 

 

 

 

 

RH-LED 

Relay C „OFF“   
Relay D „OFF“ 

Relay C „OFF“   
Relay D „OFF“ 

Relay C and/or Relay D „ON“ 

 

 

Permanent OFF setting via rotary switch 

(setting via rotary switch on C 

and

 D)

 

Measured value is below threshold value for dehumidifying 

and/or above threshold for humidifying 

(setting via rotary switch C or D) 

Measured value is above threshold for dehumidifying 

and/or below threshold for humidifying or   

Permanent ON  setting via rotary switch  

(setting via rotary switch C or D) 

 

Relative humidity below threshold 

Relative humidity above threshold 

 

Analogue control outputs 

 

Analogue control output 

Measuring range of the output 

CO

2   

0 – 10 Volt output 

500 – 2000ppm (0 – 10 Volt) 

Relative humidity 

0 – 10 Volt output 

15 – 85%RH (0 – 10 Volt) 

Temperature  

0 – 10 Volt output 

0 – 50°C (0 – 10 Volt) 