background image

Installation 

Chimney 

The chimney height and the position of the chimney terminal should conform to Building Regulations. 

Check that the chimney is in good condition, dry, free from cracks and obstructions. The diameter of the 
flue should not be less than 150mm and not more than 230mm. If any of these requirements are not met, 
the chimney should be lined by a suitable method. 

The chimney must be swept before connection to the stove. 

Where the chimney is believed to have previously served an open fire installation, it is possible that the 
higher flue gas temperature from the stove may loosen deposits that were previously firmly adhered, with 
the consequent  risk of flue blockage.   It is therefore recommended that the chimney be swept a second 
time within a month of regular use after installation. 

If you have any doubts about the suitability of your chimney, consult your local dealer/stockist. 

If  there  is  no  existing  chimney  then  either  a  prefabricated  block  chimney  in  accordance  with  Building 
Regulations Approved Document J, or a twin-walled insulated stainless steel flue to BS 4543 can be used.  
These  chimneys  must  be  fitted  in  accordance  with  the  manufacturer’s  instructions  and  Building 
Regulations. 

Flue Draught 

A  flue  draught  of  minimum  1.2mm  to  a  maximum  2.5mm  water  gauge  is  required  for  satisfactory 
appliance performance.  The flue draught should be checked under fire at high output.  If it exceeds the 
recommended maximum, a draught stabilizer must be fitted so that the rate of burning can be controlled 
and to prevent over firing. If the reading is less than the recommended minimum than the performance of 
the appliance will be compromised. 

Connection to the Chimney 

An  existing  fireplace  opening  can  be  bricked  up  or  sealed  with  a  register  plate.    A  short  length  of  flue 
pipe of a minimum 152mm internal diameter may then be used to connect the stove to the chimney.  This 
flue pipe should be of 316 grade stainless steel or vitreous enameled, nominal thickness 1.2mm.   

Ensure that the pipe end is no closer than 76mm to the side or rear chimney walls. 

Ideally, the old fireplace should be filled in so that there is a smooth streamlined entry into the flue way. 

The length of any horizontal run of flue pipe must not exceed 152mm. 

It is essential that all connections between the stove and chimney-flue are sealed and made airtight. 

Both the chimney and flue pipe must be accessible for cleaning and if ANY parts of the chimney cannot 
be reached through the stove (with baffle brick removed), a soot door must be fitted in a suitable position 
to enable this to be done. 

Air Supply 

If a draught stabilizer is fitted, the air opening should be at least 3125 mm

2

. Due consideration should be 

given to air requirements for any other appliances in the same room or space. 

 

 
 

Summary of Contents for Inglenook CEV. II

Page 1: ...your local Building Control Officer can approve the completed installation should a non accredited engineer undertake the installation It is an offence under UK law not to comply with this advice Ple...

Page 2: ...at 13 O2 0 30 Mean Flue Gas Temperature 214 C Flue Gas Mass Flow 5 5 g s Ancit Total Efficiency 68 4 Nominal Heat Output 6 0 KW Mean CO Emission at 13 O2 0 21 Mean Flue Gas Temperature 235 C Flue Gas...

Page 3: ...e must not be an extractor fan fitted in the same room as the stove as this can cause the stove to emit fumes into the room Flue Collar Place the Flue Gasket on the top or rear outlet as required Plac...

Page 4: ...ply reverse the above procedure Remove all of the Riddling Bars Cam Bar Catch Bar and Ashpan Slide the Side Brick toward the front of the Stove and pull the bottom edge into the Lift up the Side Plate...

Page 5: ...ne of these schemes your local building control department must approve the installation Scheme Web address Telephone APHC Association of Plumbing and Heating Contractors Certification Limited www aph...

Page 6: ...s required for satisfactory appliance performance The flue draught should be checked under fire at high output If it exceeds the recommended maximum a draught stabilizer must be fitted so that the rat...

Page 7: ...placed should not be less than 125mm thick and should be in accordance with the current building regulations Care should be taken to level the stove using the adjusting screws in the feet The applianc...

Page 8: ...20 mm 450 mm 120 mm 150 mm 150 mm 6 Flue Pipe Single Wall Wooden Beam 6 Flue Pipe Twin Wall Inglenook Flat Top Stove Wooden Beam All dimensions stated are minimum and assume that additional heat shiel...

Page 9: ...t least 24 hours On completion of the installation and commissioning ensure that the operating instructions and operating tools for the stove are left with the customer Advise the customer on the corr...

Page 10: ...The controls are open when they are pushed toward the outside of the Stove Secondary Air Secondary air is controlled via the Slider above the Doors It is this Airwash that keeps a clean and uninterru...

Page 11: ...tacked above the level of the rear firebrick as this may result in damage to the stove With a full load of fuel the stove will need to be refuelled approximately once every 2 hours Solid mineral fuel...

Page 12: ...It may also be necessary to adjust the tertiary air cover plate on the back of the stove To revive the fire open the air controls until the fire is burning brightly de ash if necessary and refuel Set...

Page 13: ...Persistent fume emission must not be tolerated If fume emission does persist then the following immediate action should be taken 1 Open doors and windows to ventilate room 2 Let the fire out or eject...

Page 14: ...ass and make subsequent cleaning more difficult Wet logs on heated glass a badly aimed poker or heavy slamming of the doors could crack the glass panels The glass will not fracture from heat Firebrick...

Page 15: ...allation to clear any soot falls which may have occurred due to the difference in combustion between the stove and the open fire Troubleshooting Fire will not burn Check that 1 The air inlet is not ob...

Page 16: ...s HHR08 082 Glass Gasket HHR08 081 Right Hand Door HHR08 084 Door Slider HHR08 119 Slider Knob HHR08 045 Door Knob HCR06 059 M8 Full Nut FNFM08 Catch Shaft HHR08 111 Circlip FLRX07 M8 Full Nut FNFM08...

Page 17: ...ider Shaft HHR14 073 Slider Knob HHR08 045 Flue Collar CH08 030 Flue Cover CH08 031 Side Plates HIN03 032 A B Side Bricks HIN03 031 Recouping Baffle HIN03 039 Turbo Bar HHR08 140 Rear Brick HIN03 030...

Reviews: