Hunter Stoves requests that before installation
and/or use of this appliance that you read these
instructions carefully to ensure that all the
relevant requirements are fully understood.
These instructions cover the basic principles to
ensure satisfactory installation of the stove,
although detail may need slight modification to
suit particular local site conditions. In all cases
the installation must comply with current Building
Regulations, Local Authority Byelaws, European
and National Standards and other specifications
or regulations as they affect the installation of the
stove.
It should be noted that the Building Regulations
requirements may be met by adopting the
relevant recommendations given in British
Standards BS 8303, BS 6461 and BS 7566 as an
alternative means to achieve an equivalent level
of performance to that obtained following the
guidance given in Approved Document J.
Your local Building Control Officer can advise you
regarding the interpretation of the Regulations
should there be any questions.
This appliance must be installed by a Registered
Installer (see Competent Persons Scheme) or
approved by your local Building Control Officer.
All works undertaken must be carried out with
due care and attention to meet the requirements
of the Health & Safety code of practice and any
other legislation that may have been introduced
since the publication of these instructions.
C
OMPETENT
P
ERSONS
S
CHEME
Members of the following schemes may self-
certify the installation of this stove. If the installer
is not a member of one of these schemes, your
local Building Control Department must approve
the installation.
Scheme
Web address
Telephone
APHC (Association
of Plumbing and
Heating
Contractors
(Certification)
Limited
0121 711
5030
Building
Engineering
Services
Competence
Accreditation
(BESCA Limited)
0800 652
5533
HETAS Ltd
(Heating
Equipment
Testing and
Approval Scheme)
01684
278170
NAPIT
Registration Ltd
01623
811483
NICEIC Group Ltd
0870 013
0389
F
LUE
D
RAUGHT
A flue draught of minimum 1.2mm to a maximum
2.5mm water gauge is required for satisfactory
appliance performance.
The flue draught should be checked under fire at
high output with windows and doors closed.
To take the reading cover all air intakes and put a
hole in the covering for the top air for the reader
to go through to take the reading.
If it exceeds the recommended maximum, a
draught stabiliser must be fitted so that the rate
of burning can be controlled and to prevent over
firing. If the reading is less than the recommended
minimum then the performance of the appliance
will be compromised.
C
ONNECTION TO THE CHIMNEY
/
FLUE SYSTEM
The gap between the old fireplace and stove flue
outlet must be filled in so that there is a smooth
streamlined entry into the flue way. It is essential
that all connections between the stove and
chimney-flue are sealed and made airtight. Both