background image

2

®

(Continued)

Congratulations!

Your new Hunter thermostat will provide years of reliable service. By saving energy, your thermo-
stat will pay for itself during its first season of use. Thank you for buying a Hunter product!

Please read this manual for complete instructions on installing and operating your thermostat. If
you require further assistance, call Hunter Technical Support at 1-866-268-1936 from 8am to 5pm
Central Time.

Before starting, remove the mylar label from the LCD display.

IMPORTANT INFORMATION

1. This thermostat is designed to work on the following systems:

Gas - Standing Pilot

Single-Stage Heat Pumps - with no auxiliary heat

Gas - Electronic Ignition

Electric Furnace

Gas - Fired Boilers

Electric Air Conditioning

Gas - Milivolt Systems
Oil - Fired Boilers

This thermostat will NOT control single-stage or multi-stage

Oil - Fired Furnace

heat pumps or 110/220 V baseboard electric heating systems.

2. Temperature Range

This thermostat can be programmed between 7˚C and 35˚C (45˚F and 95˚F). It will display
room temperatures from 0˚C and 37˚C (30˚F to 99˚F). “HI” will be displayed if the temperature
is higher than 37˚C (99˚F), and “LO” will be displayed if the temperature is lower than 0˚C (30˚F).

This thermostat will automatically cut-off in Heat mode if the temperature rises above 35˚C
(95˚F), and automatically cut-off in Cool mode if the temperature drops below 4˚C (40˚F).

3. Compressor Protection

This thermostat provides a 3.5 minute delay after shutting off the cooling system before it can
be restarted. This feature will prevent damage to your compressor caused by rapid cycling. It
does not prevent a rapid compressor restart due to short power outages.

4. Battery Warning

Two fresh AA alkaline batteries should provide well over one year of service. However, when
the batteries become drained, the Low Battery Indicator will flash on the display. When this
message occurs, install new alkaline batteries. You have approximately 1 minute to change
the batteries and keep thermostat’s clock and program settings. Once the batteries have
become too low to ensure proper operation, your system will be turned Off, and the display
will be cleared except for flashing Low Battery Indicator on the LCD display.

CAUTION: When only the battery icon flashes on the display, the thermo-
stat is shut down, and your system will no longer operate. In this condi-
tion, there is no temperature control of your dwelling.

NOTE: If you plan to be away from the premises over 30 days, we recommend that
you replace the old batteries with new alkaline batteries prior to leaving.

FEATURES

day/time

reset

system

heat

cool

off

program

filter

hold

/return

fan

auto

on

M

AM

4

TEMP

Hold / Return Key:

 Used for

setting a permanent (vacation)
hold, and for returning to the
normal display from Day & Time
setting, Programming, or Span
setting modes.

LCD Display:

 Shows

Time, Day, Temperature,
Program Number, and
other feature information
as required.

Low Battery Indicator:

Flashes when batteries
need to be replaced.

System Switch:

Selector switch for
Heat, Cool, and Off

Fan Switch:

 Fan

switch for Automatic
or Continuous fan
operation.

Battery Compartment:

Front access allows
easy insertion of two
AA 1.5V batteries.

Reset:

 Press with a paper clip to reset the

thermostat and return to power-up settings.

Front Door:

 Covers keys when not used for neat

appearance. Open by lifting from the bottom

Up and Down Keys:

 Keys for

changing the Temperature
setting. Also used for increasing
and decreasing selections in the
Time, Program, and Span
functions.

Day / Time Key:

 Used for entering the Clock

setting mode. Use with the Up and Down keys
to set the time and day.

Program Key:

 Used for entering

and modifying Programs. Use
with the Up and Down keys to
set times and temperatures.
Press when in Clock setting
mode to select between 12 and
24 hour clock modes.

Filter Key:

 Resets filter change

counter to zero.

Battery Release Lever:

Push to pop batteries loose.

ENERGY STAR

®

 PARTNER

As an ENERGY STAR

®

 Partner, Hunter Fan Co. has determined that this programmable thermostat

meets the ENERGY STAR

®

 guidelines for energy efficiency.

INSTALLATION

What You Need

This thermostat includes two #8 slotted screws and two wall anchors for mounting. To install
your thermostat, you should have the following tools and materials.

Slotted Screwdriver(s)

Small Philips screwdriver

Hammer

Electric drill and 3/16” bit

Two 1.5 V (AA) size alkaline batteries

Remove Old Thermostat

CAUTION: Do not remove any wiring from existing thermostat before reading the in-
structions carefully. Wires must be labeled prior to removal.

IMPORTANT! Turn off the power to the furnace at the main power panel or at the furnace.

Remove existing thermostat cover and thermostat. See Figure 1. Some thermostats will have
screws or other locking devices that must first be removed. Once the wall mounting plate is
exposed, look for wires.

If wires are not visible, they may be connected to the back of the wallplate. Again, look for
screws, tabs, etc. Some models have doors that open to expose wires and mounting screws.
See Figure 1.

Typical Home Thermostats

Wall Mounting Plate

Thermostat

Cover

Wall Mounting Plate

Thermostat

Cover

Figure 1

W

G

Y

RH

RC

Wire Labeling

Each wire coming from the wall to the existing thermostat is connected to a terminal point
on that thermostat. Each of these terminal points is usually marked with a code letter as
shown in Table A below.

Note that this thermostat has multiple function terminals that allow Single-Stage Heat
Pump capability. Standard systems use: Rh, Rc, G, W. [Single-Stage Heat Pumps use: Rh, Y1,
G, and O or B.] Table A below shows the multiple functions of the terminals. Use the termi-
nals that match your system.

The number of wires in your system can be as few as two (for heat only systems), as many
as eight, or any number in between. If you follow the labeling procedures correctly, you do
not have to be concerned about how many wires there are.

There is often no terminal marking on the existing thermostat of
two wire, heat only systems. Just connect either of the wires to
the RH terminal, then connect the other wire to the W terminal
to complete the circuit.

IMPORTANT! BEFORE DISCONNECTING ANY WIRES, APPLY THE
SELF-ADHESIVE LABELS PROVIDED TO THE WIRE AS SHOWN IN
TABLE A BELOW. (For example, attach the label marked W to the
wire that goes to the W or H terminal on your existing thermo-
stat.) IGNORE THE COLOR OF THE WIRES since these do not always comply with the standard.

Summary of Contents for Set & Save 47200A

Page 1: ...Model 47200A M AM 4 TEMP Programmable Thermostat Owners Manual ...

Page 2: ...ment Front access allows easy insertion of two AA 1 5V batteries Reset Press with a paper clip to reset the thermostat and return to power up settings Front Door Covers keys when not used for neat appearance Open by lifting from the bottom Up and Down Keys Keys for changing the Temperature setting Also used for increasing and decreasing selections in the Time Program and Span functions Day Time Ke...

Page 3: ...ting screws provided into wall anchor and tighten See Figure 3 NOTE 5 wire Systems If your thermostat has one wire marked R or RH 2 3 or 4 wire system then leave the jumper wire between the RH and RC terminals on the wallplate Otherwise if you have separate RH and RC wires 5 wire system then remove the jumper wire between the RH and RC terminals Connect Wires and Mount Thermostat to Wallplate Matc...

Page 4: ...oling mode NOTE HG position is for gas and most other systems HE position is for certain electric systems having a fan relay System Selector STANDARD HEAT PUMP switch The factory position for this switch is in the STD position Leave it in this position if you have ANY system that uses gas oil electric or hot water heating If you have a single stage Heat Pump no auxiliary or emergency heat source t...

Page 5: ...Time Temp Temp Temp Temp Sunday Time Time Time Time Temp Temp Temp Temp day time M PM day time M PM SA PM 2 TEMP day time hold return or SA PM 2 TEMP M F TH W T AM 1 HEAT program system cool heat off Cooling Day Program 1 Program 2 Program 3 Program 4 Monday Time Time Time Time Friday Temp Temp Temp Temp Saturday Time Time Time Time Temp Temp Temp Temp Sunday Time Time Time Time Temp Temp Temp Tem...

Page 6: ...H PM HOLD TEMP hold return Filter Monitor Your thermostat measures the number of hours your heating and cooling system has been in use To maximize your system s performance and energy efficiency change or clean your filter regularly When the total system runtime for heat and cool reaches 400 hours the Filter Change Indicator will flash as a reminder to check your system s filter Press to review to...

Page 7: ...t will automatically cut off in Heat mode if the room temperature rises above 35 C 95 F It will cut off in Cool mode if the room temperature drops below 4 C 40 F Note that if your system has malfunctioned and no longer responds to thermostat controls the Auto Cut Off will have no effect HEAT TEMP 2 TROUBLESHOOTING If you experience any other problems call 1 866 268 1936 from 8 AM to 5 PM Central T...

Reviews: