press
: the temperature of the cooling limit set point (in C°/F°) will be
displayed, and
indicator lights up;
➢
press
or
for 15 sec to adjust the parameter value;
➢
press
button for 15 sec to activate the cycle.
During cooling:
➢
the current probe temperature is displayed;
➢
indicator lights up;
➢
the maximum cooling temperature is set as the r4 cycle parameter;
➢
the maximum cooling time is set as the r6 cycle parameter;
➢
the operating temperature is set as the r8 cycle parameter;
➢
press
several times:
- to display the maximum remaining cooling time;
- to display
nEg
message;
- to display the chamber temperature;
- to exit the mode (or leave for 15 sec for the device exiting the mode independently).
If the temperature measured by the thermal probe reaches the set value before the set
maximum cycle time:
➢
the device switches to the storage mode;
➢
the information on the “End” of the cycle is displayed;
➢
the device provides the sound alarm;
➢
press any button to stop the sound alarm, press again to remove the “End” message.
If the temperature measured by the thermal probe does not reach the set value before the set
maximum cycle time:
➢
the cooling cycle continues;
➢
icon flashes, and
indicator lights up;
➢
the device provides the sound alarm;
➢
press
several times:
- to stop the sound alarm;
- to display the time elapsed since the set maximum cycle time;
- to display the chamber temperature;
- to display
nEg
message;
- to exit the mode (or leave for 15 sec for the device exiting the mode independently).