Typ
Tool
Minimum re-
quirements
Water pres-
sure,
bar/PSI
3.0/43.5
1.0/14.5
1.5/21.8
Water con-
sumption, l/
min /gpm
5.0/1.3
3.0/0.8
4.1/1.1
Guide values for connection to a mains
socket
The mains socket must have the same amperage as the
extension cable and the electrical socket on the product.
Note:
The nominal power must have the same voltage
+/- 10%.
DXR 145: Motor 18.5 kW
Nominal from
power source,
V
Cable area,
AWG/mm
2
Start current,
A
Motor output,
kW
Setting ther-
mal overload
relay, A
Max. cable
length, m/ft
400
6/16
75
50 Hz
18.5
27.0
285/935
400
10/6
75
18.5
27.0
100/328
400
8/10
75
18.5
27.0
175/574
460
6/16
75
60 Hz
18.5
22.0
349/1145
460
10/6
75
18.5
22.0
130/427
460
8/10
75
18.5
22.0
218/715
DXR 275: Motor 24 kW
Nominal volt-
age from pow-
er source, V
Cable area,
AWG/mm
2
Start current,
A
Motor output,
kW
Setting ther-
mal overload
relay, A
Max. cable
length, m/ft
400
7/10
99
50 Hz
24
35
345/1132
400
5/16
99
24
35
555/1821
460
7/10
99
60 Hz
24
34
355/1165
460
5/16
99
24
34
570/1870
DXR 305, DXR 315: Motor 27 kW
Nominal volt-
age from pow-
er source, V
Cable area,
AWG/mm
2
Start current,
A
Motor output,
kW
Setting ther-
mal overload
relay, A
Max. cable
length, m/ft
400
7/10
99
50 Hz
27
41
296/971
400
5/16
99
27
41
473/1552