Refrigeration Piping
The standard refrigerant will be R-404 unless otherwise
specified on the customer order. Check the serial plate on
the case for information. Refrigeration outlet access and
the refrigeration components for the Entyce are situated on
the left hand side near the centerline of the case to deliver
optimal access which provides for easy installation and
maintenance purposes without the probability of damaging
any components.
Refrigeration Lines
Liquid
Suction
3/8” O.D.
5/8” O.D.
Refrigerant lines should be sized as shown on the refrigeration
legend furnished by the store. Install P-TRAPS (oil traps) at
the base of all suction line vertical risers.
Pressure drop can
rob the system of capacity. To keep the pressure drop to a
minimum, keep refrigerant line run as short as possible, using
the minimum number of elbows. Where elbows are required,
use long radius elbows only. All refrigeration components are
located underneath the left hand side case deck pans.