IGSF-ASC-L / ASCS-L-0308
12
Low Temperature Alarm
ALLo
Low temperature
setpoint that will make the alarm go
off and the error message appear
on the display Range: from – 40 to
83°F or – 40 to 23°C
High Temperature Alarm
ALHi
High temperature
setpoint that will make the alarm go
off and the error message appear
on the display Range: from – 40 to
83°F or –40 to 23°C
Important Note: To change from degrees C to F or
vice-versa, the user must reprogram
all the parameters that are related
to the temperature. The unit does
not convert the parameters
automatically from degrees F to C
or vice-versa.
Example 1 - To adjust the time-of-day
-
Press and hold SET for 5 seconds
-
Press SET again
-
Press UP or DOWN until the correct time
appears on the display
-
Press SET to accept the new time
-
Press DOWN twice to exit the programming
mode
Example 2 - To set one defrost a day, at 11:59
PM
-
Press and hold SET and DOWN for 10
seconds
-
Press DOWN five times to get to go to the
Defrost Interval (dFIn)
-
Press SET to change the parameter
-
Press DOWN until tdAy appears on the
display
-
Press SET to accept the option
-
Press DOWN seven times to go to the
Number of Defrosts (noDF)
-
Press SET to change it
-
Press UP or DOWN until 1 appears on the
display
-
Press SET to accept the change
-
Press DOWN to go to Defrost Start Time
(dEF1)
-
Press SET to change the time
-
Press UP or DOWN until the 11:59 PM
appears on the display
-
Press SET
-
Press DOWN ten times to exit the
programming level
Error Codes
Display
Control Status
Er 1
ERC Fault – software or hardware failure
Er 2
ERC Communication Fault
– indicates that there is a problem
with the display module cable
Er 3
Zone Sensor Fault
– indicates an open or shorted
temperature sensor
Er 4
Evaporator Sensor Fault
– indicates an open or shorted
evaporator sensor
Er 5
ERC Fault – software or hardware failure
Er 6
Low Temperature Alarm
– indicates that the temperature
has dropped below the low alarm
setpoint
Er 7
High Temperature Alarm
– indicates that the temperature
has gone above the high alarm
setpoint
If the zone temperature sensor fails, the control will use
the cycle times it recorded for the last three cycles to
control the equipment (based on time). Therefore the
food will be preserved in case of failure.
If the evaporator sensor fails the control will terminate
the defrost cycle based on time.
For Error Codes 1, 2 and 5 cut the power to the unit
and correct the problem to reset the display.
For Codes 3 and 4, press the UP or DOWN button on
the display to reset the error message. If the display still
shows the message, the sensor must be replaced.
The Error Codes 6 and 7 will be automatically
reset once the temperature is back within the two
setpoints.
Technical Specifications
Input Power: 120 / 208-240 VAC 50/60 Hz (+10,-15%)
Power Consumption:
5VA @ 120/240VAC