H1 Self Contained glass front multideck

 

                         

                                                                                       Installation manual 

 

________________________________________________________________________________________________________________________
Hussmann 

 

 

                                  Page 

12

 

Trouble shooting 
 

issue 

possible reason 

remedial action  

 Product temperature is higher 

than requirement 

Store condition is warmer or more humid 

than climate class 3 (25°C/60%RH). 

Check store air conditioner operation. 

Refrigeration plant is not running or 

operating at inappropriate settings or 

conditions. 

Check for compressor unit if it is running.           

If unit is running and other possible                 

reasons are eliminated then call 

refrigeration mechanic to check plant 

operation. 

Evaporator pressure is not set correctly. 

Check suction pressure settings at the case 

and if required adjust as per                   

case specification. 

Insufficient or no air flow appears at the 

case air curtain. 

Check if case fans are turned on or 

operating correctly. If any doubt of fan 

operation contact technician. 

Check if coil is frozen up. If frozen then 

check defrost settings as per the 

manufacturers guideline or set to suite                 

the store operating condition. A colder store 

may require longer defrost               

duration. A humid store may need                    

more frequent defrost. 

Case shelf arrangement has been deviated 

significantly from original specified setup. 

Re-do the shelf arrangement as per                        

the original specification. 

Air Return is blocked by merchandise. 

Remove merchandise to behind                         

the load limit labels. 

None of above. 

Contact Hussmann. 

Products are freezing up. 

Store condition is too cold compared to 

design climate class 3. 

Check store air conditioner operation. If 

store condition cannot be lifted, then adjust 

cabinet evaporator pressure and defrost 

strategy to suite. 

Case evaporator pressure is                          

lower than specification. 

Adjust cabinet evaporator pressure                        

to suite. 

Cabinet exterior is sweating. 

Store humidity is high. 

Check store air conditioner operation. 

Insufficient ventilation. 

Check case ventilation under and at rear of 

the case. A fan kit may be needed. 

KITS: (Option Extra 

– ref Page 17) 

Case to Wall: 2500: 96A15-035 

3750: 96A15-036 

Icon Controller settings (if fitted). 

Check settings. 

Case SST. 

SST set too low. 

LED Lights are not working. 

No power supply. 

Check supply is “on” and light                         

switch is working. 

LED Lamp failed. 

Replace lamp. 

Water spill on the floor. 

 

The dissipater tray is full or leaking. 

 

Contact service provider. 

 

Store humidity is too high. 

 Boiling system is not functioning. 

 

 

Check controller, wiring, level sensor 

and heater 

 

The compressor doesn’t start 

after 2 minutes. 

The supply cables is disconnected. 

Reconnect plug. 

Summary of Contents for Austral H1

Page 1: ...ontained Multideck Case Installation Manual Reference IM 1006 The following models are covered by this Manual H1 10 H1 14 66 Glendenning Road Glendenning NSW 2761 PO Box 42 Doonside NSW 2767 t 61 2 88...

Page 2: ...e installation 2 case services dimensions 2 Operating environment 5 Handling and transporting cases 5 Shipping damages and shortages 6 Installation 6 Positioning and levelling Commissioning 7 Cleaning...

Page 3: ..._____________________________________________________________________________________ Hussmann Page 2 Pre installation Warning All refrigeration electrical and plumbing work must be carried out by lic...

Page 4: ...Self Contained Multideck _________________________________________________________________________________________________________________________ Page 3 Hussmann H1 10 Foot Print H1 14 Foot Print fi...

Page 5: ..._______________________________________________________________ Hussmann Page 4 Group Installations figure 2 acceptable group configurations NOTE Installing into an alcove is not recommended and will...

Page 6: ...Cases must not be positioned in areas that may be subject to heat or air currents such as ventilation ducts open doors or windows direct sunlight electric fans or ovens etc Otherwise the cabinet may s...

Page 7: ...trims etc are accounted for Immediately report any shipping damage to the carrier and inform Hussmann of any short supplies Installation NOTE Information in this manual is to be followed in conjuncti...

Page 8: ...any racks and shelves etc that may have been removed during installation to store requirements NOTE Incorrect shelf configurations may compromise case performance Commissioning Cleaning case Remove th...

Page 9: ...ioning Plan and risk assess the decommissioning process to include the following Isolate the case Removal of the case is to be in the reverse order of installation listed previously Disposal Case disp...

Page 10: ...n the case as this may result in personal injury and or case damage 1 Remove stock from the case and store below 5 C 2 Turn off power to the case electrical 3 Remove all price tickets and any foreign...

Page 11: ...1 Check that all case panels and trims are secure and undamaged 2 Check for rust and paint damage 3 Ensure all cable connections including screw terminals earth leads and straps are secure 4 Ensure in...

Page 12: ...t remove the protection grill clean it very carefully avoid touching other components and put the grill back in its place 14 Clean the dissipater tray To reach the dissipater tray remove the protectio...

Page 13: ...need more frequent defrost Case shelf arrangement has been deviated significantly from original specified setup Re do the shelf arrangement as per the original specification Air Return is blocked by...

Page 14: ...ce provider Rust salt or other deposits bridging the sensor input signal The sensor tip s short circuited The compressor never stops The condenser is dirty Contact service provider The fluid is missin...

Page 15: ...ched or crushed during the positioning of base trays shelves stock Staff must be trained in the correct procedures for setting up cases and ergonomic practices Slipping Drain may leak or become blocke...

Reviews: